[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934971":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},934971,605,2,"多选题","（2019年真题）根据现行国家标准《自动喷水灭火系统施工及验收规范》(GB50261)，自动喷水灭火系统调试前的必备条件有（）",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","消防水池、消防水箱储存了设计要求的水量",true,{"key":16,"text":17,"correct":14},"B","系统供电正常",{"key":19,"text":20,"correct":21},"C","湿式系统官网已经放空",false,{"key":23,"text":24,"correct":21},"D","与系统联动的火灾自动报警系统处于调试阶段",{"key":26,"text":27,"correct":14},"E","消防气压给水设备的水位、气压符合设计要求","ABE","P149-152 根据《自动喷水灭火系统施工及验收规范》7.1.2 条规定：系统调试应具备下列条件： 1 消防水池、消防水箱已储存设计要求的水量。 2 系统供电正常。 3 消防气压给水设备的水位、气压符合设计要求。 4 湿式喷水灭火系统管网内已充满水；干式、预作用喷水灭火系统管网内的气压符合设计要求；阀门均无泄漏。 5 与系统配套的火灾自动报警系统处于工作状态。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]