[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934965":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},934965,605,1,"单选题","（2019年真题）某商场安装了自动喷水灭火系统,该商场管理人员在巡查中发现湿式报警阀组漏水故障无关的是（）",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","阀瓣密闭垫老化或者损坏",false,{"key":16,"text":17,"correct":14},"B","报警阀组排水阀未完全关闭",{"key":19,"text":20,"correct":14},"C","阀瓣组件与阀座组件处有杂物",{"key":22,"text":23,"correct":24},"D","湿式报警阀组前供水控制阀未完全关闭",true,"P164-175 报警阀组漏水故障原因分析： 1) 排水阀门未完全关闭。 2) 阀瓣密封垫老化或者损坏。 3 )系统侧管道接口渗漏。 4)报警管路测试控制阀渗漏。 5 )阀瓣组件与阀座之间因变形或者污垢、杂物阻挡出现不密封状态 。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]