[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934962":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},934962,605,2,"多选题","(2016年真题) 对自动喷水灭火系统喷头的安装情况进行检查，下列说法中，正确的有（）",[11,15,18,21,25],{"key":12,"text":13,"correct":14},"A","喷头安装应在系统试压、冲洗合格后进行",true,{"key":16,"text":17,"correct":14},"B","同一隔间内不能同时安装3mm和5mm玻璃球洒水喷头",{"key":19,"text":20,"correct":14},"C","水平边墙型洒水喷头溅水盘与顶板的距离不应小于150mm，且不应大于300mm",{"key":22,"text":23,"correct":24},"D","湿式系统在吊顶下不应安装下垂型喷头",false,{"key":26,"text":27,"correct":24},"E","喷头的型号、规格，使用场所应符合规范规定","ABC","湿式系统喷头选型：吊顶下布置的喷头，应采用下垂型喷头或吊顶型喷头，故D项错误；喷头的型号、规格、使用场所应符合设计要求，故E项错误。水平式边墙型喷头溅水盘与顶板的距离为150~300mm。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]