[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934959":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},934959,605,1,"单选题","（2020年真题）某消防技术服务机构对某高层建筑的消防水泵进行了检测。根据现行国家标准《消防给水及消火栓系统技术规范》（GB50974）,下列检测结果中,不符合规范要求的是（ ）",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","以备用电源切换方式启动消防水泵,消防水泵投入正常运行用时65s",true,{"key":16,"text":17,"correct":18},"B","手动直接启动消防水泵,消防水泵投入正常运行用时20s",false,{"key":20,"text":21,"correct":18},"C","自动直接启动消防水泵,消防水泵投入正常运行用时25s",{"key":23,"text":24,"correct":18},"D","以备用泵切换方式启动消防水泵,消防水泵投入正常运行用时55s","P182-185 根据现行国家标准《消防给水及消火栓系统技术规范》（GB50974）13.1.4以备用电源切换方式或备用泵切换启动消防水泵时，消防水泵应分别在1min或2min内投入正常运行；",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]