[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934958":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},934958,605,1,"单选题","（2020年真题）根据现行国家标准《消防给水及消火栓系统技术规范》（GB50974）,对消火栓系统采用的組件、设备进行现场检验时，需要进行密封性能检查的部件是（ ）",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","减压消火栓的减压装置",false,{"key":16,"text":17,"correct":18},"B","消火栓固定接口",true,{"key":20,"text":21,"correct":14},"C","消防水带",{"key":23,"text":24,"correct":14},"D","消火栓箱","P182-185 根据现行国家标准《消防给水及消火栓系统技术规范》（GB50974），12.2.3 14消火栓固定接口应进行密封性能试验，应以无渗漏、无损伤为合格。试验数量宜从每批中抽查1%，但不应少于5个，应缓慢而均匀地升压1.6MPa，应保压2min。当两个及两个以上不合格时，不应使用该批消火栓。当仅有1个不合格时，应再抽查2%，但不应少于10个，并应重新进行密封性能试验；当仍有不合格时，亦不应使用该批消火栓。因此该题答案为B",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]