[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934957":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},934957,605,1,"单选题","（2020年真题）某办公楼，建筑高度为50m，室外消火栓管道为环状管网，消防水池仅储存室内消防用水。对该建筑的消防水源及供水设施的下列检查结果中，不符合现行国家标准要求的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","室外消火栓管道只有1路与市政供水管道连接",true,{"key":16,"text":17,"correct":18},"B","高位水箱有效消防储水量为40m3",false,{"key":20,"text":21,"correct":18},"C","室内消火栓系统与自动喷水灭火系统合用消防水泵",{"key":23,"text":24,"correct":18},"D","消防水泵接合器与最近室外消火栓的距离为18m","P175-181 根据题干描述，室外应由市政管网供水，应满足两路消防供水。因为该建筑属于高层公建，室外设计流量至少为25L\u002Fs。（室外消防设计流量满足≤20L\u002Fs时，可一路供水）。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]