[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934950":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},934950,605,1,"单选题","(2018年真题)某消防工程施工单位对系统设计工作压力为 0.8MPa 的消火栓系统进行严密性试验，下列做法中，正确的是（??）",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","试验压力 0.96MPa，稳压 12h",false,{"key":16,"text":17,"correct":14},"B","试验压力 1.0MPa，稳压 10h",{"key":19,"text":20,"correct":21},"C","试验压力 0.8MPa，稳压 24h",true,{"key":23,"text":24,"correct":14},"D","试验压力 1.2MPa，稳压 8h","水压严密性试验应在水压强度试验和管网冲洗合格后进行。试验压力应为系统工作压力，稳压24h，应无泄漏。P140-143",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]