[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934947":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},934947,605,1,"单选题","(2017年真题)某消防工程施工单位对消火栓系统进行施工前的进场检验，根据现行国家标准《消防给水及消火栓系统技术规范》GB50974，关于消火栓固定接口密封性能现场试验的说法中，正确的是（??）",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","试验数量宜从每批中抽查1%，但不应少于3个",false,{"key":16,"text":17,"correct":18},"B","当仅有1个不合格时，应再抽查2%，但不应少于10个",true,{"key":20,"text":21,"correct":14},"C","应缓慢而均匀地升压至1.6MPa，并应保压1min",{"key":23,"text":24,"correct":14},"D","当第2次抽查仍有不合格时，应继续进行批量抽查，抽查数量按前次递增","《消防给水及消火栓系统技术规范》(GB 50974)中规定，消火栓的现场检验应符合下列要求：消火栓固定接口应进行密封性能试验，应以无渗漏、无损伤为合格。试验数量宜从每批中抽查1％，但不应少于5个，应缓慢而均匀地升压至1．6 MPa，并保压2 min。当2个及2个以上不合格时，不应使用该批消火栓。当仅有1个不合格时，应再抽查2％，但不应少于10个，并应重新进行密封性能试验；当仍有不合格时，亦不应使用该批消火栓。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]