[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934946":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},934946,605,1,"单选题","(2017年真题)根据现行国家标准《消防给水及消火栓系统技术规范》GB50974，干式消火栓系统允许的最大充水时间是（ ）min",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","10",false,{"key":16,"text":17,"correct":18},"B","5",true,{"key":20,"text":21,"correct":14},"C","2",{"key":23,"text":24,"correct":14},"D","3","1.7.1.6 干式消火栓系统因为其内充满有压空气，打开消火栓后先要排气，然后才能出水，因出水滞后而影响灭火，所以本次规范规定了充水时间。 现行国家标准《建筑设计防火规范》GB 50016-2006和《高层民用建筑设计防火规范》GB 50045-95等规范对于干式系统没有充水时间的规定，但现行国家标准《建筑设计防火规范》GB 50016-2006第12.2.2条第3款干式系统充水时间不应大于90s，该参数过小，致使隧道内的干式系统要分成若干子系统，造成管道系统复杂，投资增加。 发达国家的标准有10min和3min的充水规定，本次规范综合考虑确定为5min。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]