[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934943":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},934943,605,1,"单选题","（2020年真题）对某高层办公建筑的消防给水系统进行维护保养的下列做法，不符合现行国家标准《消防给水及消火栓系统技术规范》（GB 50974）的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","每日检查一次消防水池、高位消防水箱的水位",false,{"key":16,"text":17,"correct":18},"B","每季度模拟自动控制条件自动启动消防水泵运转—次",true,{"key":20,"text":21,"correct":14},"C","每月手动启动消防水泵运转一次",{"key":23,"text":24,"correct":14},"D","每月检测一次气压水罐的压力和有效容积","P171-173 《消防给水及消火栓系统技术规范》，14.0.4消防水泵和稳压泵等供水设施的维护管理应符合下列规定:1每月应手动启动消防水泵运转一次，并应检查供电电源的情况﹔故选项B不符合。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]