[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934940":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},934940,605,1,"单选题","（2020年真题）某消防技术服务机构对某高层建筑的室内消火栓系统进行了检测,消防后,屋顶试验用消火栓出水压力低于设计值。下列原因分析中,可以排除的是（ ）",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","消防水泵出水管道阀门未完全开启",false,{"key":16,"text":17,"correct":14},"B","安装在消防水泵出口的超压泄水装置的动作压力设定值过低",{"key":19,"text":20,"correct":14},"C","管网内存在参与气体",{"key":22,"text":23,"correct":24},"D","消防水泵吸水管存在气囊",true,"P148-154 屋顶试验用消火栓出水压力低于设计值说明水泵运转不正常，系统漏水或管道不通畅，故A,B,C均有可能。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]