[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934938":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},934938,605,1,"单选题","(2015年真题) 根据《消防给水及消火栓系统技术规范》（GB50974-2014）的规定，室内消火栓系统管网安装完成后，对其进行水压试验和冲洗的正确顺序是（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","强度试验--严密性试验--冲洗",false,{"key":16,"text":17,"correct":18},"B","强度试验--冲洗--严密性试验",true,{"key":20,"text":21,"correct":14},"C","冲洗--强度试验--严密性试验",{"key":23,"text":24,"correct":14},"D","冲洗--严密性试验--强度试验","管网安装完毕后，应对其进行强度试验、冲洗和严密性试验。水压强度试验的测试点应设在系统管网的最低点。对管网注水时，应将管网内的空气排净，井应缓慢升压，达到试验压力后，稳、压30 min ，管网应无泄漏、无变形，且压力降不应大 于0.05 MPa。管网冲洗应在试压合格后分段进行。冲洗顺序应先室外、后室内，先地下、后地上。室内部分的冲洗应按配水干管、配水管、配水支管的顺序进行;管网冲洗结束后，应将管网内的水排除干净。水压严密性试验应在水压强度试验和管网冲洗合格后进行。试验压力应为设计工作压力，稳序， 24h ，应无泄漏。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]