[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934932":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},934932,605,1,"单选题","(2018年真题)某消防工程施工单位对已安装的消防水泵进行调试，水泵的额定流量为 30L\u002Fs，扬程为 100m，系统设计工作压力为 1.0MPa。下列调试结果中，符合现行国家标准《消防给水及消火栓系统技术规范》(GB 50974)的是（ ）",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","自动直接启动消防水泵时，消防水泵在 60s 时投入正常运行",false,{"key":16,"text":17,"correct":18},"B","消防水泵零流量时，水泵出水口压力表的显示压力为 1.30MPa",true,{"key":20,"text":21,"correct":14},"C","以备用电源的切换方式启动消防水泵时，消防水泵在 2min 时投入正常运行",{"key":23,"text":24,"correct":14},"D","消防水泵出口流量为 45L\u002Fs 时，出口处压力表显示未为0.55MPa","水泵零流量时水泵出水口压力宜为系统设计工作压力的1.2～1.4倍. P118-132",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]