[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934927":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},934927,605,2,"多选题","(2016年真题) 下列关于消防水泵接合器的安装要求的说法中，正确的有（??）",[11,15,18,21,25],{"key":12,"text":13,"correct":14},"A","应安装在便于消防车接近使用的地点",true,{"key":16,"text":17,"correct":14},"B","墙壁式消防水泵接合器不应安装在玻璃墙下方",{"key":19,"text":20,"correct":14},"C","墙壁式消防水泵接合器与门窗洞口的净距不应小于2.0m",{"key":22,"text":23,"correct":24},"D","距室外消火栓或消防水池的距离以为5m-40m",false,{"key":26,"text":27,"correct":24},"E","地下消防水泵接合器进水口与井盖底部的距离不应小于井盖的直径","ABC","水泵接合器接口的位置应方便操作，安装在便于消防车接近的人行道或非机动车行驶地段，距室外消火栓或消防水池的距离宜为15～40 m；墙壁水泵接合器的安装应符合设计要求。设计无要求时，其安装高度距地面宜为0．7 m；与墙面上的门、窗、孔洞的净距离不应小于2．0 m，且不应安装在玻璃幕墙下方。地下水泵接合器的安装，应使进水口与井盖底面的距离不大于0．4 m，且不应小于井盖的半径；井内应有足够的操作空间并应做好防水和排水措施，防止地下水渗入。寒冷地区井内应做防冻保护。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]