[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934924":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},934924,605,1,"单选题","(2016年真题)某消防检测机构，检查物业公司的临时高压消防给水系统维护管理记录，发现有一条维护管理记录如下：自动和手动启动消防水泵时，水泵无法实现运转，按下控制柜的机械应急启动操纵杆时，水泵能正常运转。下来关于系统故障的原因中，正确的是（??）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","自动巡检变频器故障",false,{"key":16,"text":17,"correct":18},"B","控制电器元件故障",true,{"key":20,"text":21,"correct":14},"C","电机供电回路故障",{"key":23,"text":24,"correct":14},"D","供电电压不足","机械应急可以启动，自动或手动启动不了，说明是控制电器元件出现了故障，故B 正确。 选项A 只会影响自动巡检功能；选项C 、D 也会影响应急操作时水泵的启动和运转:选项B 涉及到自动和手动启动消防水泵的控制电器元件，如继电器等。应急启动类似于直接把回路闭合，自动和手动启动是通过继电器等使回路闭合，启动水泵，故B 正确。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]