[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934919":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},934919,605,1,"单选题","(2018年真题) 对某高层公共建筑消防给水系统进行维护检测，消防水泵测试阀开启，水泵出水干管上的压力开关动作后，消防水泵未启动。下列故障原因分析中，可排除的是（??）",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","消防联动控制器处于手动状态",true,{"key":16,"text":17,"correct":18},"B","压力开关与水泵之间线路故障",false,{"key":20,"text":21,"correct":18},"C","消防水泵控制柜处于手动启泵状态",{"key":23,"text":24,"correct":18},"D","消防水泵控制柜内继电器损坏","消防水泵出水干管上的压力开关动作后，消防水泵应连锁启动，不受联动控制器处于自动或者手动状态的影响。P132-133",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]