[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934918":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},934918,605,2,"多选题","(2017年真题) 某服装加工厂，室内消防采用临时高压消防给水系统联合供水，稳压泵稳压，系统设计流量57L\u002Fs，室外供水干管采用DN200球磨铸铁管，埋地敷设，长度为2000m。消防检测机构现场检测结果为：室外管网漏水率为2.40L\u002F(min?km），室内管网部分漏水量为0.2L\u002Fs,该系统管网总泄漏量计算和稳压泵设计流量正确的有（??）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","管网泄漏量0.28L\u002Fs，稳压泵设计流量1.0L\u002Fs",true,{"key":16,"text":17,"correct":18},"B","管网泄漏量0.20L\u002Fs，稳压泵设计流量0.28L\u002Fs",false,{"key":20,"text":21,"correct":14},"C","管网泄漏量0.28L\u002Fs，稳压泵设计流量1.28L\u002Fs",{"key":23,"text":24,"correct":18},"D","管网泄漏量0.20L\u002Fs，稳压泵设计流量1.0L\u002Fs",{"key":26,"text":27,"correct":18},"E","管网泄漏量0.28L\u002Fs，稳压泵设计流量0.5L\u002Fs","AC","室外管网漏损量：2．4×2÷60=0．08(L／s)，管网总泄漏量：0．2+0．08=0．28(L／s)。稳压泵设计流量不小于室外漏损量，且不小于1．00L／s。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]