[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934914":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},934914,605,2,"多选题","（2019年真题）某商业综合体建筑高度为31.6m，总建筑面积为35000㎡，设置临时高压消防给水系统。根据现行国家标准《消防给水及消火栓系统技术规范》(GB50974)，对消火栓系统进行验收下列验收检测结果中，不符合规范要求的有（）",[11,15,18,21,25],{"key":12,"text":13,"correct":14},"A","消防主泵切换到备用泵的时间为60秒",false,{"key":16,"text":17,"correct":14},"B","联动控制器属于手动状态时，高位消防水箱的消火栓出水干管的流量开关动作，消防水泵启动",{"key":19,"text":20,"correct":14},"C","消防水泵启动后不能自动停止运行",{"key":22,"text":23,"correct":24},"D","消防水泵吸水管上的控制阀采用暗杆闸阀，无开启刻度和标志",true,{"key":26,"text":27,"correct":24},"E","高位消防水箱有效容积为36m3，设置有水位报警装置","DE","P118-132 消防水泵的吸水管上应设置明杆闸阀或带自锁装置的蝶阀，但当设置暗杆闸阀门时，应设有开启刻度和标志，故D选项说法错误 总建筑面积大于30000㎡的商店建筑，高位消防水箱容积不应小于50m3，故E选项说法错误",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]