[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934913":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},934913,605,1,"单选题","（2019年真题）某高层公共建筑消防给水系统的系统工作压力为1.25MPa，选用的立式消防水泵参数为流量40L\u002Fs，扬程100m，对该系统进行验收前检测，下列检测结果中，不符合现行国家标准要求的是（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","停泵时，压力表显示水锤消除设施后的压力为1.3MPa",false,{"key":16,"text":17,"correct":18},"B","流量计显示出水流量为60L\u002Fs时，压力表显示为0.6MPa",true,{"key":20,"text":21,"correct":14},"C","手动直接启泵，消防水泵在36s时投入正常运行",{"key":23,"text":24,"correct":14},"D","吸水管上的控制阀锁定在常开位置，并有明显标记","P118-132 当出流量为设计流量的150%时，其出口压力不应低于设计工作压力的65%。 所以，当出流量为60L\u002Fs时，水泵出口压不应低于0.65MPa，",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]