[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934912":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},934912,605,1,"单选题","（2019年真题）某超高层建筑高度为230m，塔楼功能为酒店、办公，裙房为商业。对该建筑消防设施进行验收检测，下列检测结果中，不符合现行国家标准要求的是（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","采用消防水泵转输水箱串联供水，转输水箱有效储水容积为50m3",true,{"key":16,"text":17,"correct":18},"B","比例式减压阀垂直安装，水流方向向下",false,{"key":20,"text":21,"correct":18},"C","塔楼酒店客房洒水喷头采用快速响应喷头",{"key":23,"text":24,"correct":18},"D","第三十层酒店大堂采用隐蔽型喷头","P118-132 当采用消防水泵转输水箱串联时，转输水箱的有效储水容积不应小于60m3，转输水箱可作为高位消防水箱。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]