[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934887":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},934887,605,2,"多选题","（2020年真题）某建筑高度为36m、耐火等级为二级的商场，设有自动喷水灭火系统和火灾自动报警系统，该商场建筑外墙外保温和外墙装饰的下列做法中，不符合现行国家标准的有（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","选用燃烧性能为B1级的燃材料作为外墙外保温材料",true,{"key":16,"text":17,"correct":14},"B","电气线路穿金属管保护后直接敷设在燃烧性能为B1级的外保温材料中",{"key":19,"text":20,"correct":21},"C","选用燃烧性能为B1级的材料作为外墙装饰材料",false,{"key":23,"text":24,"correct":21},"D","选用燃烧性能为B1级的材料作为屋面外墙保温材料。",{"key":26,"text":27,"correct":21},"E","二层外墙外保温系统不燃材料防护层厚度为10mm","AB","P128-130 根据《建筑设计防火规范》选项A，商场为人密场所，故外墙外保温材料应采用A级材料;则A选项不正确。选项B，电气线路不应穿越或敷设在燃烧性能为B1或B2级的保温材料中;确需穿越或敷设时，应采取穿金属管并在金属管周围采用不燃隔热材料进行防火隔离等防火保护措施.故B错误。选项C，建筑高度不超过50m，可以采用B1级的材料作为外墙装饰材料。故C正确。选项D，不管屋面板是否满足1h的耐火极限，B1级都足够。故D正确。选项E，首层不燃材料防护层厚度≥15mm，其他楼层防护层厚度≥5mm。故E正确。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]