[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934858":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},934858,605,1,"单选题","（2019年真题）对某植物油加工厂房的浸出车间进行防火检查，下列对通风系统检查的结果中，不符合现行国家标准要求的是（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","送风机采用普通型的通风设备，布置在单独分隔的通风机房内，送风干管上设置了防止回流设施",false,{"key":16,"text":17,"correct":18},"B","排风管道穿过防火墙时两侧均设置防火阀",true,{"key":20,"text":21,"correct":14},"C","排风系统采用了导除静电的接地装置",{"key":23,"text":24,"correct":14},"D","排风机采用防爆型设备","P93-95 厂房内用于有爆炸危险场所的排风管道，严禁穿过防火墙和有爆炸危险的房间隔墙。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]