[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934854":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},934854,605,1,"单选题","（2020年真题）对某地下商场进行防火检查时，发现有两个防火分区与避难走道连通，其中防火分区一设置两个净宽为1.4m的门通向该避难走道防烟前室。防火分区二设置一个净宽为1.40m的门通向该避难走道防烟前室，下列防火检查中符合现行国家标准的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","避难走道的净宽度为3.00m",true,{"key":16,"text":17,"correct":18},"B","避难走道入口处前室的建筑面积为6.0m2",false,{"key":20,"text":21,"correct":18},"C","商场开向避难走到前室的门为乙级防火门",{"key":23,"text":24,"correct":18},"D","避难走道顶棚装修材料为珍珠岩吸声板","P106-108 避难走道的净宽度不得小于任一防火分区通向该避难走道的设计疏散总净宽度，A正确。避难走道入口处前室的使用面积不小于6.0m2，B不正确。C不正确，商场开向避难走到前室的门应为甲级防火门。D不正确，顶棚需采用不燃材料装修。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]