[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934838":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},934838,605,1,"单选题","(2017年真题)对某医院的高层病房楼进行防火检查时，发现下列关于避难间的做法中，错误的是（??）",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","在二层及以上的病房楼层设置避难间",false,{"key":16,"text":17,"correct":14},"B","避难间靠近楼梯间设置，采用耐火极限为2.50h的防火隔墙和甲级防火门与其他部位隔开",{"key":19,"text":20,"correct":14},"C","每个避难间为2个护理单元服务",{"key":22,"text":23,"correct":24},"D","每个避难间的建筑面积为25m2",true,"《建筑设计防火规范》(GB50016—2014)第5．5．24条规定，高层病房楼应在二层及以上的病房楼层和洁净手术部设置避难间(选项A正确)。避难间应符合下列规定：①避难间服务的护理单元不应超过2个(选项C正确)，其净面积应按每个护理单元不小于25．0m2确定(选项D错误，建筑面积为25m2，则净面积达不到25m2)。②避难间兼作其他用途时，应保证人员的避难安全，且不得减少可供避难的净面积。③应靠近楼梯间，并应采用耐火极限不低于2．00h的防火隔墙和甲级防火门与其他部位分隔(选项B正确)。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]