[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934818":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},934818,605,2,"多选题","（2019年真题）某建材商场，地下3层，地上5层，建筑高度为30m，地上每层建筑面积为8000㎡，划分为2个防火分区。对该商场的下列防火检查结果中不符合现行国家标准要求的有（）",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","空调通风管道穿越楼梯间，采用金属风管",false,{"key":16,"text":17,"correct":14},"B","第四层营业厅的最大疏散距离为35m",{"key":19,"text":20,"correct":21},"C","因搬运大件货物需要，有1部疏散楼梯入口处采用防火卷帘分隔",true,{"key":23,"text":24,"correct":21},"D","水暖管道井的检修门开向楼梯间，采用甲级防火门",{"key":26,"text":27,"correct":14},"E","地上第三层人员密度为0.13人\u002F㎡，该疏散楼梯的总净宽度为11m","CD","P77-82 民用建筑及厂房的疏散门应采用向疏散方向开启的平开门，不应采用推拉门、卷帘门、吊门、转门和折叠门。故C选项说法错误 水暖管道井的检修门不应在楼梯间内开设，故D选项错误",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]