[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934810":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},934810,605,1,"单选题","（2019年真题）某造纸厂干燥车间，耐火等级为二级，地上2层，每层划分4个防火分区，地下局部1层，划分为2个防火分区。该车间采用自动化生产工艺，平时只有巡检人员。对该车间的下列防火检查结果中，不符合现行国家标准要求的是（）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","首层的最大疏散距离为60m",false,{"key":16,"text":17,"correct":14},"B","地下一层1个防火分区的其中1个安全出口借用相邻防火分区疏散",{"key":19,"text":20,"correct":14},"C","首层外门的净宽度为1.2m",{"key":22,"text":23,"correct":24},"D","地上二层1个防火分区的其中1个安全出口借用相邻防火分区疏散",true,"P77-82 地下或半地下厂房(包括地下或半地下室)，当有多个防火分区相邻布置，并采用防火墙分隔时，每个防火分区可利用防火墙上通向相邻防火分区的甲级防火门作为第二安全出口，但每个防火分区必须至少有1个直通室外的独立安全出口。地上部分不能借用，故选项B正确，",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]