[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934804":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},934804,605,1,"单选题","（2019年真题）某建筑髙度为30m的写字楼,标准层建筑面积为800㎡，人均使用面积为6㎡,采用剪刀楼梯间。对该写字楼的下列防火检查结果中,符合现行国家标准要求的是（）",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","楼梯间共用一套机械加压送风系统",false,{"key":16,"text":17,"correct":18},"B","梯段之间隔墙的耐火极限为2.00h",true,{"key":20,"text":21,"correct":14},"C","其中一间办公室门至最近安全出口的距离为15m",{"key":23,"text":24,"correct":14},"D","梯段的净宽度为1.1m","P83-86 剪刀楼梯间的加压送风系统不能共用，故A选项错误 住宅单元和高层公共建筑的疏散楼梯，当分散设置确有困难，且任一户门或从任一疏散门至最近疏散楼梯间入口的距离不大于10m时，可采用剪刀楼梯间。故C选项说法错误 题目中建筑为高层建筑，楼梯宽度不应小于1.2m,故D选项说法错误",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]