[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934774":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},934774,605,2,"多选题","（2020年真题）某消防技术服务机构对某高层建筑进行消防安全评估，下列检查结果中符合现行国家标准要求的有（ ）。",[11,15,18,21,25],{"key":12,"text":13,"correct":14},"A","油浸变压器室开向建筑内的门采用乙级防火门",false,{"key":16,"text":17,"correct":14},"B","开向相邻防火分区的门采用乙级防火门",{"key":19,"text":20,"correct":14},"C","避难层内设备间开向避难层区的门采用乙级防火门",{"key":22,"text":23,"correct":24},"D","电梯候梯厅通往地下汽车库的出口采用乙级防火门",true,{"key":26,"text":27,"correct":24},"E","消防控制室开向建筑内的门采用乙级防火门","DE","P88-98 参《建筑设计防火规范》5.5.6直通建筑内附设汽车库的电梯，应在汽车库部分设置电梯候梯厅，并应采用耐火极限不低于2.00h的防火隔墙和乙级防火门与汽车库分隔。故选项D正确。5.5.23建筑高度大于100m的公共建筑，应设置避难层（间）。避难层（间）应符合下列规定:4.管道井和设备间应采用耐火极限不低于2.00h的防火隔墙与避难区分隔，管道井和设备间的门不应直接开向避难区;确需直接开向避难区时，与避难层区出入口的距离不应小于5m，且应采用甲级防火门。故选项C错误。6.2.7通风、空气调节机房和变配电室开向建筑内的门应采用甲级防火门，消防控制室和其他设备房开向建筑内的门应采用乙级防火门。故选项E正确。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]