[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934762":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},934762,605,2,"多选题","(2018年真题)某大型地下商业建筑，占地面积30000㎡。下列对该建筑防火分隔措施的检查结果中，不符合现行国家标准要求的有( )。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","消防控制室房间门采用乙级防火门",false,{"key":16,"text":17,"correct":18},"B","空调机房房间门采用乙级防火门",true,{"key":20,"text":21,"correct":14},"C","气体灭火系统储瓶间房间门采用乙级防火门",{"key":23,"text":24,"correct":18},"D","变配电室房间门采用乙级防火门",{"key":26,"text":27,"correct":18},"E","通风机房房间门采用乙级防火门","BDE","通风、空调机房和变配电室开向建筑内的门应采用甲级防火门，消防控制室和其他设备房间开向建筑内的门应采用乙级防火门。消防水泵房的门应采用甲级防火门；消防电梯机房与普通电梯机房之间采用耐火极限不低于2.00h 的隔墙分开，如开门，应设甲级防火门。P68-75",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]