[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934758":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},934758,605,1,"单选题","(2018年真题)对某建筑进行防火检查，变形缝的下列检查结果中，不符合现行国家标准要求的是( )",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","变形缝的填充材料采用防火枕",false,{"key":16,"text":17,"correct":14},"B","空调系统的风管穿越防火分隔处的变形缝时，变形缝两侧风管设置公称动作温度为70℃的防火阀",{"key":19,"text":20,"correct":21},"C","在可燃气体管道穿越变形缝处加设了阻燃PVC套管",true,{"key":23,"text":24,"correct":14},"D","变形缝的构造基层采用镀锌钢板","阻燃PVC套管属于难燃材料，不能用于可燃气体管道套管。P61-66",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]