[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934741":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},934741,605,2,"多选题","(2017年真题) 下列防火分隔措施的检查结果中， 不符合现行国家消防技术标准的有（）",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","铝合金轮载抛光厂房采用3.00h耐火极限的防火墙划分防火分区",true,{"key":16,"text":17,"correct":14},"B","电石仓库采用3.00h耐火极限的防火墙划分防火分区",{"key":19,"text":20,"correct":21},"C","高层宾馆防火墙两侧的窗采用乙级防火窗， 窗洞之间最近边缘的水平距离为1.0m",false,{"key":23,"text":24,"correct":14},"D","烟草成品库采用3.00h耐火极限的防火墙划分防火分区",{"key":26,"text":27,"correct":21},"E","通风机房开向建筑内的门采用甲级防火门， 消防控制室开向建筑内的门采用乙级防火门","ABD","铝合金轮毂抛光厂房为乙类，乙类厂房应采用耐火极限不低于4．00 h的防火墙划分防火分区，故选项A错误。电石仓库为甲类，甲类仓库应采用耐火极限不低于4．00 h的防火墙划分防火分区，故选项B错误。防火墙两侧的窗采用乙级防火窗，窗洞之间的水平距离不限，故选项C正确。烟草成品库为丙类，丙类库房应采用耐火极限不低于4．00 h的防火墙划分防火分区，故选项D错误。通风、空气调节机房和变配电室开向建筑内的门应采用甲级防火门，消防控制室和其他设备房开向建筑内的门应采用乙级防火门，故选项E正确。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]