[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934735":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},934735,605,1,"单选题","（2019年真题）某总建筑面积为33000㎡的地下商场,分隔为两个建筑面积不大于2000㎡的区域,区域之间采用防火隔间进行连通。对防火隔间的下列检查结果中,符合现行国家标准要求的是（）",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","防火隔间的围护构件采用耐火极限为2.00h的防火隔墙",false,{"key":16,"text":17,"correct":14},"B","防火隔间呈长方形布置，长边为3m，短边为2m",{"key":19,"text":20,"correct":14},"C","通向防火隔间的门作为疏散门",{"key":22,"text":23,"correct":24},"D","防火隔间门的耐火极限为1.50h",true,"P68-75 防火隔间的要求： 建筑面积不应小于6㎡ 隔墙应采用耐火极限不低于3.00h的防火隔墙，故A选项说法错误 应采用甲级防火门，故D选项正确 不同防火分区通向防火隔间的门最小间距不应小于4m，长3m，宽2m,两扇门之间的距离小于4m,不满足要求，故B选项错误 防火隔间只能用于相邻两个独立使用场所的人员互相通行，不得用于除人员通行外的其他用途，故C选项错误",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]