[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934729":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},934729,605,1,"单选题","（2019年真题）某10层办公楼，建筑高度为36m，标准层建筑面积为3000㎡，设置有自动喷水灭火系统，外墙采用玻璃幕墙。对该办公楼的下列防火检查结果中，不符合现行国家标准要求的是（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","九层、十层外墙上、下层开口之间防火玻璃墙的耐火极限为0.50h",true,{"key":16,"text":17,"correct":18},"B","一至四层外墙上、下层开口之间采用高度为0.80m的实体墙分隔",false,{"key":20,"text":21,"correct":18},"C","五至八层外墙上、下层开口之间采用高度为1.20m的实体墙分隔",{"key":23,"text":24,"correct":18},"D","标准层采用大空间办公，每层为1个防火分区","P61-66 如果上、下层开口之间因实体墙设置有困难，采用防火玻璃墙分隔，对于高层建筑，防火玻璃墙的耐火完整性不应低于1.00h，对于多层建筑，防火玻璃墙的耐火完整性不应低于0.5h。本题目中建筑高度36m，为高层建筑，防火玻璃墙耐火完整性不应低于1.00h，故A选项说法错误。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]