[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934681":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},934681,605,1,"单选题","（2019年真题）某松节油生产厂房专用的10kV变电站贴邻厂房设置。该厂房的下列防火防爆做法中，不符合现行国家标准要求的是（）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","生产厂房贴邻变电站的墙体为防火墙",false,{"key":16,"text":17,"correct":14},"B","贴邻的防火墙设置了一扇不可开启的甲级防火窗",{"key":19,"text":20,"correct":14},"C","厂房的所有电器均采用防爆电器",{"key":22,"text":23,"correct":24},"D","厂房与变电站连通开口处设置了甲级防火门",true,"P48-57 松节油生产厂房为乙类厂房。 变、配电所不应设置在甲、乙类厂房内或贴邻建造，且不应设置在爆炸性气体、粉尘环境的危险区域内。供甲、乙类厂房专用的10KV及以下的变、配电站，当采用无门、窗、洞口的防火墙隔开时，可一面贴邻。乙类厂房的配电所必须在防火墙上开窗时，应设置密封固定的甲级防火窗。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]