[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934674":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},934674,605,2,"多选题","(2016年真题) 某丙类厂房建筑高度为45m，对其消防救援窗口进行防火检查。下列消防救援窗口设置的做法中，符合规范要求的有（）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","消防救援窗口采取易碎安全玻璃，并在外侧设置明显标志",true,{"key":16,"text":17,"correct":18},"B","每个防火分区设置1个消防救援窗口",false,{"key":20,"text":21,"correct":18},"C","消防救援窗口设置在3层以上楼层",{"key":23,"text":24,"correct":14},"D","消防救援窗口的净高和净宽约为1.20m",{"key":26,"text":27,"correct":14},"E","消防救援窗口的下沿距地面室内高度为1.2m","ADE","选项B错误，参考《建规》7.2.5，消防救援窗口设置位置应该与消防车登高操作场地相对应，每个防火分区不应少于2个。选项C错误，参考《建规》7.2.4：“厂房、仓库、公共建筑的外墙应在每层的适当位置设置可供消防救援人员进入的窗口。”@##",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]