[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"lib-604-6":3},{"library":4,"page":9,"limit":10,"total":11,"questions":12,"related":629},{"id":5,"name":6,"category":7,"favorite":8},604,"消防安全技术实务(一级)","建筑工程",0,6,50,2960,[13,34,46,58,70,82,94,112,124,136,148,160,172,184,196,208,220,232,247,259,271,282,294,306,318,330,342,354,366,377,392,404,416,428,440,452,461,476,488,497,509,521,533,542,554,569,581,593,605,617],{"id":14,"libraryId":5,"type":15,"typeLabel":16,"stem":17,"options":18,"answer":27,"analysis":33},931936,1,"单选题","（2019年真题）某公共建筑，建筑高度为98m，地下3层，地上30层，防烟楼梯间和前室均设有机械加压送风系统且地上部分与地下部分加压送风系统分别独立设置。关于该加压送风系统设计的说法，正确的是（）",[19,23,26,30],{"key":20,"text":21,"correct":22},"A","地上楼梯间顶部应设置不小于2㎡的固定窗",false,{"key":24,"text":25,"correct":22},"B","前室的计算风量仅考虑着火层所需风量",{"key":27,"text":28,"correct":29},"C","地上楼梯间送风系统竖向可不分段设置",true,{"key":31,"text":32,"correct":22},"D","前室的计算风量仅考虑着火层和上一层所需风量","",{"id":35,"libraryId":5,"type":15,"typeLabel":16,"stem":36,"options":37,"answer":31,"analysis":33},931937,"（2019年真题）当采用自然排烟方式时，储烟仓的厚度不应小于空间净高的（），且不应小于500mm，同时储烟仓底部距地面的高度应大于安全疏散所需的最小清晰高度。",[38,40,42,44],{"key":20,"text":39,"correct":22},"25%",{"key":24,"text":41,"correct":22},"15%",{"key":27,"text":43,"correct":22},"10%",{"key":31,"text":45,"correct":29},"20%",{"id":47,"libraryId":5,"type":15,"typeLabel":16,"stem":48,"options":49,"answer":20,"analysis":33},931938,"（2019年真题）某两层办公建筑每层划分为一个防火分区，其防烟楼梯间和前室均设有机械加压送风系统，第三层的2只独立感烟火灾探测器发出火灾报警信号后，下列消防联动控制器的控制功能，符合规范要求的是（）",[50,52,54,56],{"key":20,"text":51,"correct":29},"前室送风口开启后，联动控制前室加压送风机的启动",{"key":24,"text":53,"correct":22},"联动控制该建筑楼梯间所有送风口的开启",{"key":27,"text":55,"correct":22},"能手动控制前室，楼梯间送风口的开启",{"key":31,"text":57,"correct":22},"联动控制第二层，三层，四层，前室送风口开启",{"id":59,"libraryId":5,"type":15,"typeLabel":16,"stem":60,"options":61,"answer":20,"analysis":33},931939,"（2020年真题）某建筑面积为220m2的会议室，室内净空高度为3.2m，设有机械排烟设施,该会议室的机械排烟量至少应为（ ）m3\u002Fh.",[62,64,66,68],{"key":20,"text":63,"correct":29},"15000",{"key":24,"text":65,"correct":22},"13200",{"key":27,"text":67,"correct":22},"15840",{"key":31,"text":69,"correct":22},"26400",{"id":71,"libraryId":5,"type":15,"typeLabel":16,"stem":72,"options":73,"answer":27,"analysis":33},931940,"（2020年真题）某造纸厂房,室内净空高度为5m,采用自然排烟方式。该车间防烟分区内的任一点与最近自然排烟窗之间的水平距离最大可为（ ）m.",[74,76,78,80],{"key":20,"text":75,"correct":22},"30.0",{"key":24,"text":77,"correct":22},"37.5",{"key":27,"text":79,"correct":29},"14.0",{"key":31,"text":81,"correct":22},"20.0",{"id":83,"libraryId":5,"type":15,"typeLabel":16,"stem":84,"options":85,"answer":31,"analysis":33},931941,"（2020年真题）某建筑高度为99m的办公楼,地下2层,地上31层，防烟楼梯间和前室均设有机械加压送风系统,且地上部分与地下部分的加压送风系统分别独立设置。关于加压送风系统设置的说法,错误的是（ ）。",[86,88,90,92],{"key":20,"text":87,"correct":22},"该建筑地上部分的机械加压送风系统可不分段独立设置",{"key":24,"text":89,"correct":22},"前室应每层设一个常闭式加压送风口,并应设手动开启装置",{"key":27,"text":91,"correct":22},"采用机械加压送风的场所不宜设置可开启外窗",{"key":31,"text":93,"correct":29},"送风机的进风口与排烟口在同一面上时,两者的水平距离不应小于15m",{"id":95,"libraryId":5,"type":96,"typeLabel":97,"stem":98,"options":99,"answer":111,"analysis":33},931942,2,"多选题","（2020年真题）关于加压送风系统控制的说法，正确的有（ ）。",[100,102,104,106,108],{"key":20,"text":101,"correct":29},"加压送风机应能现场手动启动",{"key":24,"text":103,"correct":29},"加压送风机应能通过火灾自动报警系统自动启动",{"key":27,"text":105,"correct":29},"加压送风机应能在消防控制室手动启动",{"key":31,"text":107,"correct":22},"防火分区内确认火灾后，应能在20s内联动开启加压送风机",{"key":109,"text":110,"correct":29},"E","系统中任一常闭加压送风口开启时，加压风机应能自动启动","ABCE",{"id":113,"libraryId":5,"type":15,"typeLabel":16,"stem":114,"options":115,"answer":27,"analysis":33},931943,"（2017真题）集中电源集中控制型消防应急照明和疏散指示系统不包括（ ）。",[116,118,120,122],{"key":20,"text":117,"correct":22},"分配电装置",{"key":24,"text":119,"correct":22},"应急照明控制器",{"key":27,"text":121,"correct":29},"输入模块",{"key":31,"text":123,"correct":22},"疏散指示灯具",{"id":125,"libraryId":5,"type":15,"typeLabel":16,"stem":126,"options":127,"answer":20,"analysis":33},931944,"（2018真题）某地铁地下车站，消防应急照明和疏散指示系统由一台应急照明控制器、2台应急照明电箱和 50 只消防应急照明灯具组成。现有3只消防应急灯具损坏需要更换，更换消防应急灯具可选类型（）。",[128,130,132,134],{"key":20,"text":129,"correct":29},"自带电源集中控制型",{"key":24,"text":131,"correct":22},"集中电源非集中控制型",{"key":27,"text":133,"correct":22},"自带电源非集中控制型",{"key":31,"text":135,"correct":22},"集中电源集中控制型",{"id":137,"libraryId":5,"type":15,"typeLabel":16,"stem":138,"options":139,"answer":27,"analysis":33},931945,"（2015真题）下列场所中，应在疏散走道和主要疏散路径的地面上增设能保持视觉连续的疏散指示标志的是（）。",[140,142,144,146],{"key":20,"text":141,"correct":22},"总建筑面积为6000m2的展览厅",{"key":24,"text":143,"correct":22},"座位数为1200个的剧场",{"key":27,"text":145,"correct":29},"总筑面积为500m2的电子游艺厅",{"key":31,"text":147,"correct":22},"总建筑面积为500m2的地下超市",{"id":149,"libraryId":5,"type":15,"typeLabel":16,"stem":150,"options":151,"answer":20,"analysis":33},931946,"（2018真题）某小型机场航站楼，消防应急照明和疏散指示系统由1台消防应急照明控制器、1台应急照明集中电源、3台应急照明分配点装置和100只消防应急灯具组成。当应急照明系统由正常工作状态转为应急状态时，发出应急转换控制信号，但消防应急灯具未点亮。据此，可以排除的故障原因是（ ）。",[152,154,156,158],{"key":20,"text":153,"correct":29},"消防应急灯具电池衰减无法保证灯具转入应急工作",{"key":24,"text":155,"correct":22},"应急照明控制器未向应急照明集中电源发出联动控制信号",{"key":27,"text":157,"correct":22},"系统内应急照明分配电源未转入应急输出",{"key":31,"text":159,"correct":22},"系统内应急照明分配电装置未转入应急输出",{"id":161,"libraryId":5,"type":15,"typeLabel":16,"stem":162,"options":163,"answer":27,"analysis":33},931947,"（2016真题）下列建筑中的消防应急照明备用电源的连续供电时间按1.0h设置，其中不符 合规范要求的是（ ）。",[164,166,168,170],{"key":20,"text":165,"correct":22},"医疗建筑、老年人建筑",{"key":24,"text":167,"correct":22},"总建筑面积大于100000㎡的商业建筑",{"key":27,"text":169,"correct":29},"建筑高度大于于100m的住宅建筑",{"key":31,"text":171,"correct":22},"总建筑面积大于干20000㎡的地下汽车库",{"id":173,"libraryId":5,"type":15,"typeLabel":16,"stem":174,"options":175,"answer":24,"analysis":33},931950,"（2019年真题）某商场设置了集中控制型消防应急照明和疏散指示系统，灯具采用自带蓄电池电源供电。关于系统组成的说法，正确的是()",[176,178,180,182],{"key":20,"text":177,"correct":22},"该系统应由应急照明控制器，应急照明分配电装置和自带电源型灯具及相关附件组成",{"key":24,"text":179,"correct":29},"该系统应由应急照明控制器，应急照明配电箱和自带电源型灯具及相关附件组成",{"key":27,"text":181,"correct":22},"该系统应由应急照明控制器，应急照明集中电源、应急照明分配电装置和自带电源型灯具及相关附件组成",{"key":31,"text":183,"correct":22},"该系统应由应急照明控制器，应急照明集中电源和自带电源型灯具及相关附件组成",{"id":185,"libraryId":5,"type":15,"typeLabel":16,"stem":186,"options":187,"answer":27,"analysis":33},931951,"（2019年真题）某大型KTV场所设置了集中控制型消防应急照明和疏散指示系统。该场所下列消防应急灯具的选型中，正确的是()",[188,190,192,194],{"key":20,"text":189,"correct":22},"主要疏散通道地面上采用自带电源A型地埋式标志灯",{"key":24,"text":191,"correct":22},"采用的地埋式标志灯的防护等级为IP65",{"key":27,"text":193,"correct":29},"净高3.3m的疏散走道上方采用小型标志灯",{"key":31,"text":195,"correct":22},"楼梯间采用蓄光型指示标志",{"id":197,"libraryId":5,"type":15,"typeLabel":16,"stem":198,"options":199,"answer":27,"analysis":33},931952,"（2020年真题）下列场所或部位中，可不独立设置照明配电箱的是（ ）。",[200,202,204,206],{"key":20,"text":201,"correct":22},"商场营业厅的防火分区",{"key":24,"text":203,"correct":22},"住宅建筑的防烟楼梯间",{"key":27,"text":205,"correct":29},"办公楼的敞开楼梯间",{"key":31,"text":207,"correct":22},"病房楼的防火分区",{"id":209,"libraryId":5,"type":15,"typeLabel":16,"stem":210,"options":211,"answer":27,"analysis":33},931953,"（2020年真题）关于A型消防应急灯具的说法，错误的是（ ）。",[212,214,216,218],{"key":20,"text":213,"correct":22},"A型消防应急灯具包括A型应急照明灯具和A型应急疏散标志灯具",{"key":24,"text":215,"correct":22},"自带电源A型消防应急灯具蓄电池电源的额定工作电压可为DC24V",{"key":27,"text":217,"correct":29},"集中电源A型消防应急灯具的主电源和蓄电池电源的电压等级可不同",{"key":31,"text":219,"correct":22},"集中电源A型消防应急灯具主电源的额定工作电压可为DC36V",{"id":221,"libraryId":5,"type":15,"typeLabel":16,"stem":222,"options":223,"answer":20,"analysis":33},931954,"（2020年真题）某应急照明集中电源，额定输出功率为720W，额定输出电压为DC36v，输出回路为4个。当应急照明集中电源各输出回路的额定输出电流一致时，每个回路配接灯具的最大额定工作电流总和为（ ）。",[224,226,228,230],{"key":20,"text":225,"correct":29},"4A",{"key":24,"text":227,"correct":22},"10A",{"key":27,"text":229,"correct":22},"6A",{"key":31,"text":231,"correct":22},"5A",{"id":233,"libraryId":5,"type":96,"typeLabel":97,"stem":234,"options":235,"answer":246,"analysis":33},931955,"（2020年真题）关于消防应急照明灯具设置部位的地面最低水平照度的说法，正确的有（ ）。",[236,238,240,242,244],{"key":20,"text":237,"correct":22},"养老院疏散走道的地面最低水平照度不应低于5.0lx",{"key":24,"text":239,"correct":22},"屋顶直升机停机坪的地面最低水平照度不应低于5.0lx",{"key":27,"text":241,"correct":29},"病房楼楼梯间的地面最低水平照度不应低于10.0lx",{"key":31,"text":243,"correct":29},"观众厅疏散走道的地面最低水平照度不应低于3.0lx",{"key":109,"text":245,"correct":22},"教学楼疏散楼梯的地面最低水平照度不应低于5.0lx","CD",{"id":248,"libraryId":5,"type":15,"typeLabel":16,"stem":249,"options":250,"answer":24,"analysis":33},931956,"（2016真题）城市消防远程监控系统由用户信息传输装置、报警传输网络、监控中心和 ( )等部分组成。",[251,253,255,257],{"key":20,"text":252,"correct":22},"用户服务系统",{"key":24,"text":254,"correct":29},"火警信息终端",{"key":27,"text":256,"correct":22},"报警受理系统",{"key":31,"text":258,"correct":22},"远程查岗系统",{"id":260,"libraryId":5,"type":15,"typeLabel":16,"stem":261,"options":262,"answer":20,"analysis":33},931957,"（2018真题）下列关于城市消防远程监控系统设计正确的是（）。",[263,265,267,269],{"key":20,"text":264,"correct":29},"城市消防远程监控系统应能同时接收和处理不少于3个联网用户的火灾报警信息",{"key":24,"text":266,"correct":22},"城市消防远程监控系统向城市消防通信指挥中心或其他接处警中心转发经确认的火灾报警信息的时间不应大于5s",{"key":27,"text":268,"correct":22},"城市消防远程监控系统的火灾报警信息、建筑消防设施运行状态信息等记录应备份，其保存周期不应小于6个月",{"key":31,"text":270,"correct":22},"城市消防远程监控系统录音文件的保存周期不应少于3个月",{"id":272,"libraryId":5,"type":15,"typeLabel":16,"stem":273,"options":274,"answer":31,"analysis":33},931958,"（2017真题）城市消防远程监控系统不包括()。",[275,277,279,280],{"key":20,"text":276,"correct":22},"用户信息传输装置",{"key":24,"text":278,"correct":22},"报警传输网络",{"key":27,"text":254,"correct":22},{"key":31,"text":281,"correct":29},"火灾报警控制器",{"id":283,"libraryId":5,"type":15,"typeLabel":16,"stem":284,"options":285,"answer":20,"analysis":33},931959,"（2017真题）关于灭火器配置计算修正系数的说法，错误的是（ ）。",[286,288,290,292],{"key":20,"text":287,"correct":29},"同时设置室内消火栓系统，灭火系统和火灾自动报警系统时，修正系数为0.3",{"key":24,"text":289,"correct":22},"仅设置室内消火栓系统时，修正系统为0.9",{"key":27,"text":291,"correct":22},"仅设有灭火系统时，修正系统为0.7",{"key":31,"text":293,"correct":22},"同时设置室内消火栓系统和灭火系统时，修正系统为0.5",{"id":295,"libraryId":5,"type":15,"typeLabel":16,"stem":296,"options":297,"answer":27,"analysis":33},931960,"（2015真题）某多层民用建筑的第二层为舞厅，建筑面积为1000m2。该场所设有室内消火栓系统、自动喷水灭火系统、火灾自动报警系统及防排烟系统，并按严重危险等级配置灭火器。若在该层设置3个灭火器设置点，每处设置干粉灭火器2具，则每具灭火器的灭火级别应为（ ）。",[298,300,302,304],{"key":20,"text":299,"correct":22},"2A",{"key":24,"text":301,"correct":22},"21B",{"key":27,"text":303,"correct":29},"3A",{"key":31,"text":305,"correct":22},"55B",{"id":307,"libraryId":5,"type":15,"typeLabel":16,"stem":308,"options":309,"answer":31,"analysis":33},931961,"（2016真题）与其他手提式灭火器相比，手提式二氧化碳灭火器的结构特点是（ ）。",[310,312,314,316],{"key":20,"text":311,"correct":22},"取消了压力表，增加虹吸管",{"key":24,"text":313,"correct":22},"取消了安全阀，增加了虹吸管",{"key":27,"text":315,"correct":22},"取消了安全阀，增加了压力表",{"key":31,"text":317,"correct":29},"取消了压力表，增加了安全阀",{"id":319,"libraryId":5,"type":15,"typeLabel":16,"stem":320,"options":321,"answer":27,"analysis":33},931962,"（2018真题）根据现行国家标准《建筑灭火器配置设计规范》（GB50140）下列配置灭火器的场所中，危险等级属于严重危险级的是（ ）。",[322,324,326,328],{"key":20,"text":323,"correct":22},"中药材库房",{"key":24,"text":325,"correct":22},"酒精度数小于60度的白酒库房",{"key":27,"text":327,"correct":29},"工厂分控制室",{"key":31,"text":329,"correct":22},"电脑、电视机等电子产品库房",{"id":331,"libraryId":5,"type":15,"typeLabel":16,"stem":332,"options":333,"answer":24,"analysis":33},931963,"（2018真题）某综合楼的变配电室找配置灭火。该配电室应配置的灭火器是（ ）。",[334,336,338,340],{"key":20,"text":335,"correct":22},"水基型灭火器",{"key":24,"text":337,"correct":29},"磷酸铵盐干粉灭火器",{"key":27,"text":339,"correct":22},"泡沫灭火器",{"key":31,"text":341,"correct":22},"装有金属喇叭筒的二氧化碳灭火器",{"id":343,"libraryId":5,"type":15,"typeLabel":16,"stem":344,"options":345,"answer":27,"analysis":33},931964,"（2018真题）某服装加工厂,共4层,建筑高度23m,呈矩形布置,长40m，宽25m,设有室内消栓系统和自动喷水灭火系统,该服装加工厂拟配置MF\u002FABC3型手提式灭火器,每层配置的灭火数量至少应为（ ）。",[346,348,350,352],{"key":20,"text":347,"correct":22},"6具",{"key":24,"text":349,"correct":22},"5具",{"key":27,"text":351,"correct":29},"4具",{"key":31,"text":353,"correct":22},"3具",{"id":355,"libraryId":5,"type":15,"typeLabel":16,"stem":356,"options":357,"answer":20,"analysis":33},931965,"（2015真题）某白酒灌装车间设置推车式灭火器，应优先选择的是（ ）",[358,360,362,364],{"key":20,"text":359,"correct":29},"抗溶性泡沬灭火器",{"key":24,"text":361,"correct":22},"清水灭火器",{"key":27,"text":363,"correct":22},"水雾灭火器",{"key":31,"text":365,"correct":22},"碳酸氢钠干粉灭火器",{"id":367,"libraryId":5,"type":15,"typeLabel":16,"stem":368,"options":369,"answer":20,"analysis":33},931966,"（2016真题）在对可燃纤维织物加工车间配置灭火器时，除水基型灭火器外，下列灭火器中，应选择（ ）",[370,372,374,376],{"key":20,"text":371,"correct":29},"轻水泡沫灭火器",{"key":24,"text":373,"correct":22},"卤代烷灭火器",{"key":27,"text":375,"correct":22},"二氧化碳灭火器",{"key":31,"text":365,"correct":22},{"id":378,"libraryId":5,"type":96,"typeLabel":97,"stem":379,"options":380,"answer":391,"analysis":33},931967,"（2017真题）关于古建筑灭火器配置的说法，错误的有（ ）",[381,383,385,387,389],{"key":20,"text":382,"correct":22},"县级以上的文物保护古建筑，单具灭火器最小配置灭火级别是3A",{"key":24,"text":384,"correct":29},"县级以上的文物保护古建筑，单位灭火级别最大保护面积是60m2\u002FA",{"key":27,"text":386,"correct":29},"县级以上的文物保护古建筑，单具灭火器最小配置灭火级别是2A",{"key":31,"text":388,"correct":29},"县级以上的文物保护古建筑，单位灭火级别最大保护面积是90m2\u002FA",{"key":109,"text":390,"correct":29},"县级以上的文物保护古建筑，单位灭火级别最大保护面积是75m2\u002FA","BCDE",{"id":393,"libraryId":5,"type":15,"typeLabel":16,"stem":394,"options":395,"answer":24,"analysis":33},931968,"（2017真题）下列场所灭火器配置方案中，错误的是（ ）",[396,398,400,402],{"key":20,"text":397,"correct":22},"商场女装库房配置水型灭火器",{"key":24,"text":399,"correct":29},"碱金属（钾，钠）库房配置水型灭火器",{"key":27,"text":401,"correct":22},"食用油库房配置泡沫灭火器",{"key":31,"text":403,"correct":22},"液化石油气罐瓶间配置干粉灭火器",{"id":405,"libraryId":5,"type":15,"typeLabel":16,"stem":406,"options":407,"answer":31,"analysis":33},931969,"（2017真题）下列火灾中，不应采用碳酸氢钠干粉灭火的是（ ） 。",[408,410,412,414],{"key":20,"text":409,"correct":22},"可燃气体火灾",{"key":24,"text":411,"correct":22},"易燃，可燃液体火灾",{"key":27,"text":413,"correct":22},"可溶化固体火灾",{"key":31,"text":415,"correct":29},"可燃固体表面火灾",{"id":417,"libraryId":5,"type":15,"typeLabel":16,"stem":418,"options":419,"answer":27,"analysis":33},931970,"（2018真题）根据现行国家标准《自动灭火器配置设计规范》，下列建筑灭火器的配置方案中正确的是（ ）。",[420,422,424,426],{"key":20,"text":421,"correct":22},"某办公楼，将1间计算机房与5间办公室，作为一个计算单元配置灭火器",{"key":24,"text":423,"correct":22},"某酒店建筑，首层门厅与二层相通，两层按照一个计算单元配置灭火器",{"key":27,"text":425,"correct":29},"某电子游戏厅，建筑面积150㎡，配置MF\u002FABC4型手提灭火器",{"key":31,"text":427,"correct":22},"某教学楼，配置MF\u002FABC3型手提灭火器，最大保护半径25m",{"id":429,"libraryId":5,"type":15,"typeLabel":16,"stem":430,"options":431,"answer":24,"analysis":33},931971,"（2017真题）灭火器组件不包括（ ）。",[432,434,436,438],{"key":20,"text":433,"correct":22},"筒体，阀门",{"key":24,"text":435,"correct":29},"压力开关",{"key":27,"text":437,"correct":22},"压力表，保险销",{"key":31,"text":439,"correct":22},"虹吸管，密封阀",{"id":441,"libraryId":5,"type":15,"typeLabel":16,"stem":442,"options":443,"answer":20,"analysis":33},931972,"（2015真题）某场所配置的灭火器型号为“MF\u002FABC10”。下列对该灭火器类型、规格的说明中，正确的是（ ）。",[444,446,448,450],{"key":20,"text":445,"correct":29},"该灭火器是10kg手提式（磷酸铵盐）干粉灭火器",{"key":24,"text":447,"correct":22},"该灭火器是10kg推车式（磷酸铵盐）干粉灭火器",{"key":27,"text":449,"correct":22},"该灭火器是10L手提式（碳酸氨钠）干粉灭火器",{"key":31,"text":451,"correct":22},"该灭火器是10L手提式（磷酸铵盐）干粉灭火器",{"id":453,"libraryId":5,"type":15,"typeLabel":16,"stem":454,"options":455,"answer":27,"analysis":33},931973,"（2015真题）地下汽车库配置灭火器时，计算单元的最小需配灭火级别计算应比地上汽车库增加（ ）",[456,457,458,460],{"key":20,"text":43,"correct":22},{"key":24,"text":45,"correct":22},{"key":27,"text":459,"correct":29},"30%",{"key":31,"text":39,"correct":22},{"id":462,"libraryId":5,"type":96,"typeLabel":97,"stem":463,"options":464,"answer":475,"analysis":33},931974,"（2019年真题）某地上商场，总建筑面积为4000㎡, 设置自动喷水灭火系统，采用直立型标准覆盖面积洒水喷头。 该喷头布置中，错误的有()",[465,467,469,471,473],{"key":20,"text":466,"correct":29},"喷头呈正方形布置，边长为3. 8m",{"key":24,"text":468,"correct":29},"喷头呈平行四边形布置，长边和短边分别为3. 5m和1. 5m",{"key":27,"text":470,"correct":22},"喷头呈长方形布直，长边和短边分别为4. 0m和3.0m",{"key":31,"text":472,"correct":29},"喷头与端墙的距离为2. 0m",{"key":109,"text":474,"correct":22},"喷头与端墙的距离为0. 2m","ABD",{"id":477,"libraryId":5,"type":15,"typeLabel":16,"stem":478,"options":479,"answer":20,"analysis":33},931975,"（2019年真题）影响灭火器配置数量的主要因素不包括（）。",[480,482,484,486],{"key":20,"text":481,"correct":29},"建筑物的耐火等级",{"key":24,"text":483,"correct":22},"建筑的使用性质",{"key":27,"text":485,"correct":22},"火灾蔓延速度",{"key":31,"text":487,"correct":22},"火灾扑救难易程度",{"id":489,"libraryId":5,"type":15,"typeLabel":16,"stem":490,"options":491,"answer":20,"analysis":33},931976,"（2019年真题）下列灭火器中，不适合扑救A类火灾的是（ ）",[492,493,494,496],{"key":20,"text":365,"correct":29},{"key":24,"text":373,"correct":22},{"key":27,"text":495,"correct":22},"泡沫灭火器水",{"key":31,"text":337,"correct":22},{"id":498,"libraryId":5,"type":15,"typeLabel":16,"stem":499,"options":500,"answer":24,"analysis":33},931977,"（2019年真题）某低温冷库拟配置手提式灭火器，可以选择的类型、规格是（）。",[501,503,505,507],{"key":20,"text":502,"correct":22},"MP\u002FAR6",{"key":24,"text":504,"correct":29},"MF\u002FABC3",{"key":27,"text":506,"correct":22},"MS\u002FT6",{"key":31,"text":508,"correct":22},"MP6",{"id":510,"libraryId":5,"type":15,"typeLabel":16,"stem":511,"options":512,"answer":27,"analysis":33},931978,"（2019年真题）某教学楼，建筑高度为8m，每层建筑面积为1000㎡，共2层，第一层为学生教室，第二层为学生教室及教研室，该教学楼拟配置MF\u002FABC4型手提式灭火器， 下列配置方案中，正确的是（）",[513,515,517,519],{"key":20,"text":514,"correct":22},"当室内设有消火栓系统和灭火系统时，至少应配置6具灭火器",{"key":24,"text":516,"correct":22},"当室内设有灭火系统和自动报警系统时，至少应配置8具灭火器",{"key":27,"text":518,"correct":29},"当室内设有消火栓和自动报警系统时，至少应配置12具灭火器",{"key":31,"text":520,"correct":22},"当室内未设有消火栓和灭火系统时，至少应配置16具灭火器",{"id":522,"libraryId":5,"type":15,"typeLabel":16,"stem":523,"options":524,"answer":20,"analysis":33},931979,"（2019年真题）关于B类火灾场所灭火器配置的设法，正确的是（）",[525,527,529,531],{"key":20,"text":526,"correct":29},"中危险级单位灭火级别最大保护面积为1.0㎡",{"key":24,"text":528,"correct":22},"每个设置点的灭火器数量不宜多于3具",{"key":27,"text":530,"correct":22},"轻危险级单具灭火器最小配置灭火级别为27B",{"key":31,"text":532,"correct":22},"严重危险级单具灭火器最小配置灭火级别为79B",{"id":534,"libraryId":5,"type":15,"typeLabel":16,"stem":535,"options":536,"answer":27,"analysis":33},931980,"（2020年真题）下列灭火器中，不适用于扑救E类火灾的是（ ）。",[537,539,540,541],{"key":20,"text":538,"correct":22},"磷酸铵盐干粉天火器",{"key":24,"text":365,"correct":22},{"key":27,"text":339,"correct":29},{"key":31,"text":375,"correct":22},{"id":543,"libraryId":5,"type":15,"typeLabel":16,"stem":544,"options":545,"answer":24,"analysis":33},931981,"（2020年真题）下列建筑或场所中，均应按中危险级配置灭火器的是（ ）。",[546,548,550,552],{"key":20,"text":547,"correct":22},"电缆廊道、工厂的分控室、卷烟厂包装厂房",{"key":24,"text":549,"correct":29},"变压器油灌桶间、沥青加工厂房、植物油加工精炼部位",{"key":27,"text":551,"correct":22},"油淬火处理车间、木工厂厂房、氟利昂厂房",{"key":31,"text":553,"correct":22},"中药材库房、谷物筒仓工作塔、原木库房",{"id":555,"libraryId":5,"type":96,"typeLabel":97,"stem":556,"options":557,"answer":568,"analysis":33},931982,"（2020年真题）某建筑高度为15m的3层公共建筑,每层建筑面积为1000m2，设有消火栓系统和自动喷水灭火系统。该建筑—层为超市,二层为电子游戏厅,三层为电影院。关于该建筑灭火器配置的说法,正确的有（ ）。",[558,560,562,564,566],{"key":20,"text":559,"correct":29},"超市的营业厅、电子游戏厅、电影院的观众厅应分别作为一个计算单元",{"key":24,"text":561,"correct":29},"计算单元的最小需配灭火级别的修正系数可取0.5",{"key":27,"text":563,"correct":29},"电子游戏厅单具灭火器最小配置灭火级别应为3A",{"key":31,"text":565,"correct":29},"电影院观众厅单具灭火器最小配置灭火级别应为2A",{"key":109,"text":567,"correct":22},"超市单具灭火器最小配置灭火级别应为3A","ABCD",{"id":570,"libraryId":5,"type":15,"typeLabel":16,"stem":571,"options":572,"answer":31,"analysis":33},931983,"（2017真题）下列消防配电设计方案中，符合规范要求的是（ ）。",[573,575,577,579],{"key":20,"text":574,"correct":22},"消防水泵电源由建筑一层低压分配电室出线",{"key":24,"text":576,"correct":22},"消防电梯配电线路采用树干式供电",{"key":27,"text":578,"correct":22},"消防配电线路设置过负载保护装置",{"key":31,"text":580,"correct":29},"排烟风机两路电源在排烟机房内自动切换",{"id":582,"libraryId":5,"type":15,"typeLabel":16,"stem":583,"options":584,"answer":27,"analysis":33},931984,"（2016真题）某高层宾馆，下列关于消防设备配电装置的做法中，不能满足消防设备供电要求的是（ ）。",[585,587,589,591],{"key":20,"text":586,"correct":22},"引至消防泵的两路电源在泵房内末端自动切换",{"key":24,"text":588,"correct":22},"消防负荷的配电线路设置短路动作保护装置",{"key":27,"text":590,"correct":29},"消防负荷的配电线路设置过负荷和过、欠电压保护装置",{"key":31,"text":592,"correct":22},"消防负荷的配电线路未设置剩余电流保护装置",{"id":594,"libraryId":5,"type":15,"typeLabel":16,"stem":595,"options":596,"answer":20,"analysis":33},931985,"（2016真题）某建筑面积为70000m2，建筑高度为80m的办公建筑，下列供电电源中，不能满足该建筑消防用电设备供电要求的是（ ）。",[597,599,601,603],{"key":20,"text":598,"correct":29},"由城市一个区域变电站引来2路电源，并且每根电缆均能承受100%的负荷",{"key":24,"text":600,"correct":22},"由城市不同的两个区域变电站引来两路电源",{"key":27,"text":602,"correct":22},"由城市两个不同的发电厂引来两路电源",{"key":31,"text":604,"correct":22},"由城市一个区域变电站引来一路电源，同时设置一台自备发电机组",{"id":606,"libraryId":5,"type":15,"typeLabel":16,"stem":607,"options":608,"answer":20,"analysis":33},931986,"（2015真题）某建筑高度为50m的宾馆，采用一路市政电源供电，柴油发电设备作为备用电源，建筑内的排烟风机采用主备电源自动切换装置。下列关于主备电源自动切换装置的设置中，不合理的是（ ）。",[609,611,613,615],{"key":20,"text":610,"correct":29},"自动切换装置设置在变电站内",{"key":24,"text":612,"correct":22},"自动切换装置设置在排烟风机房的风机控制配电箱内",{"key":27,"text":614,"correct":22},"主备电源自动切换时间为20s",{"key":31,"text":616,"correct":22},"主备电源自动切换时间为25s",{"id":618,"libraryId":5,"type":15,"typeLabel":16,"stem":619,"options":620,"answer":31,"analysis":33},931987,"（2018真题）可以安装在消防配电线路上，以保证消防用电设备供电安全性和可靠性的装置是（ ）。",[621,623,625,627],{"key":20,"text":622,"correct":22},"过流保护装置",{"key":24,"text":624,"correct":22},"剩余电流动作保护装置",{"key":27,"text":626,"correct":22},"欠压保护装置",{"key":31,"text":628,"correct":29},"短路保护装置",[630,633,636,639,642,645],{"id":15,"name":631,"category":7,"favorite":632},"领导干部任职前廉政法规知识测试题",92,{"id":634,"name":635,"category":7,"favorite":15},595,"建筑结构与设备",{"id":637,"name":638,"category":7,"favorite":15},715,"招标采购专业知识与法律法规",{"id":640,"name":641,"category":7,"favorite":15},848,"市政方向-通用基础",{"id":643,"name":644,"category":7,"favorite":8},534,"BIM工程师",{"id":646,"name":644,"category":7,"favorite":8},535]