[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"lib-604-57":3},{"library":4,"page":9,"limit":10,"total":11,"questions":12,"related":593},{"id":5,"name":6,"category":7,"favorite":8},604,"消防安全技术实务(一级)","建筑工程",0,57,50,2960,[13,34,46,58,70,82,94,105,117,129,138,150,160,172,184,196,207,219,231,243,254,264,273,285,297,308,320,331,343,355,367,379,389,401,409,419,431,443,455,467,479,491,503,515,527,539,549,560,572,581],{"id":14,"libraryId":5,"type":15,"typeLabel":16,"stem":17,"options":18,"answer":27,"analysis":33},934513,1,"单选题","除住宅外，多层建筑内的厨房隔墙耐火极限及隔墙上防火门窗等级分别是（ ）。",[19,23,26,30],{"key":20,"text":21,"correct":22},"A","≥1.00h，乙级",false,{"key":24,"text":25,"correct":22},"B","≥1.50h，乙级",{"key":27,"text":28,"correct":29},"C","≥2.00h，乙级",true,{"key":31,"text":32,"correct":22},"D","≥2.50h，甲级","",{"id":35,"libraryId":5,"type":15,"typeLabel":16,"stem":36,"options":37,"answer":24,"analysis":33},934514,"根据《建筑设计防火规范》，建筑内的防火隔墙应从楼地面基层隔断至梁、楼板或屋面板的底面基层。住宅分户墙和单元之间的墙应隔断至梁、楼板或屋面板的底面基层，屋面板的耐火极限不应低于（ ）h。",[38,40,42,44],{"key":20,"text":39,"correct":22},"0.4h",{"key":24,"text":41,"correct":29},"0.5h",{"key":27,"text":43,"correct":22},"1.0h",{"key":31,"text":45,"correct":22},"1.5h",{"id":47,"libraryId":5,"type":15,"typeLabel":16,"stem":48,"options":49,"answer":20,"analysis":33},934515,"室内不设自喷的建筑外墙上、下层开口之间应设置高度不小于（ ）的实体墙，或挑出宽度不小于（ ）、长度不小于开口宽度的防火挑檐。",[50,52,54,56],{"key":20,"text":51,"correct":29},"1.2m；1.0m",{"key":24,"text":53,"correct":22},"0.8m；1.0m",{"key":27,"text":55,"correct":22},"1.0m；0.8m",{"key":31,"text":57,"correct":22},"0.8m，1.0m",{"id":59,"libraryId":5,"type":15,"typeLabel":16,"stem":60,"options":61,"answer":20,"analysis":33},934516,"某省级电视塔外墙采用玻璃幕墙，建筑幕墙应在每层楼板外沿处应设置高度不小于（ ）m的实体墙或挑出宽度不小于1.0m、长度不小于开口宽度的防火挑檐。",[62,64,66,68],{"key":20,"text":63,"correct":29},"1.2",{"key":24,"text":65,"correct":22},"1.0",{"key":27,"text":67,"correct":22},"0.8",{"key":31,"text":69,"correct":22},"0.6",{"id":71,"libraryId":5,"type":15,"typeLabel":16,"stem":72,"options":73,"answer":24,"analysis":33},934517,"附设在建筑物内的消防控制室应采用耐火极限不低于（ ）的隔墙与其他部位隔开，隔墙上的门应采用（ ）防火门。Ⅰ、2.0h；Ⅱ、2.5hⅢ、甲级；Ⅳ、乙级",[74,76,78,80],{"key":20,"text":75,"correct":22},"Ⅰ、Ⅲ",{"key":24,"text":77,"correct":29},"Ⅰ、Ⅳ",{"key":27,"text":79,"correct":22},"Ⅱ、Ⅲ",{"key":31,"text":81,"correct":22},"Ⅱ、Ⅳ",{"id":83,"libraryId":5,"type":15,"typeLabel":16,"stem":84,"options":85,"answer":20,"analysis":33},934518,"根据《建筑设计防火规范》，设置在丁、戊类厂房中的通风机房应采用耐火极限不低于（ ）的隔墙和0.50h的楼板与其它部位隔开。",[86,88,90,92],{"key":20,"text":87,"correct":29},"1.00h",{"key":24,"text":89,"correct":22},"2.00h",{"key":27,"text":91,"correct":22},"3.00h",{"key":31,"text":93,"correct":22},"1.50h",{"id":95,"libraryId":5,"type":15,"typeLabel":16,"stem":96,"options":97,"answer":27,"analysis":33},934519,"根据《建筑设计防火规范》，电缆井、管道井、排烟道、排气道、垃圾道等竖向管道井的井壁应为耐火极限不低于（ ）h的不燃性；井壁上的检查门应采用丙级防火门。",[98,100,102,104],{"key":20,"text":99,"correct":22},"0.80",{"key":24,"text":101,"correct":22},"1.20",{"key":27,"text":103,"correct":29},"1.00",{"key":31,"text":45,"correct":22},{"id":106,"libraryId":5,"type":15,"typeLabel":16,"stem":107,"options":108,"answer":27,"analysis":33},934520,"根据《建筑设计防火规范》，电缆井、管道井、排烟道、排气道、垃圾道等竖向管道井，应分别独立设置；井壁上的检查门应采用（ ）防火门。",[109,111,113,115],{"key":20,"text":110,"correct":22},"甲级",{"key":24,"text":112,"correct":22},"乙级",{"key":27,"text":114,"correct":29},"丙级",{"key":31,"text":116,"correct":22},"丁级",{"id":118,"libraryId":5,"type":15,"typeLabel":16,"stem":119,"options":120,"answer":31,"analysis":33},934521,"建筑高度为110m的高层建筑，其电缆井和管道井应（ ）在楼板处设防火封堵。",[121,123,125,127],{"key":20,"text":122,"correct":22},"每隔一层",{"key":24,"text":124,"correct":22},"每隔两至三层",{"key":27,"text":126,"correct":22},"每隔三至四层",{"key":31,"text":128,"correct":29},"每层",{"id":130,"libraryId":5,"type":15,"typeLabel":16,"stem":131,"options":132,"answer":27,"analysis":33},934522,"电缆井、管道井等井壁上的检查门应采用（ ）的防火门。",[133,134,135,136],{"key":20,"text":110,"correct":22},{"key":24,"text":112,"correct":22},{"key":27,"text":114,"correct":29},{"key":31,"text":137,"correct":22},"不限",{"id":139,"libraryId":5,"type":15,"typeLabel":16,"stem":140,"options":141,"answer":20,"analysis":33},934523,"根据《建筑设计防火规范》，电线电缆、可燃气体和甲、乙、丙类液体的管道不宜穿过建筑内的变形缝；当必须穿过时，应在穿过处加设（ ）制作的套管或采取其它防变形措施，并应采用防火封堵材料封堵。",[142,144,146,148],{"key":20,"text":143,"correct":29},"不燃材料",{"key":24,"text":145,"correct":22},"塑料",{"key":27,"text":147,"correct":22},"防水材料",{"key":31,"text":149,"correct":22},"难燃材料",{"id":151,"libraryId":5,"type":15,"typeLabel":16,"stem":152,"options":153,"answer":27,"analysis":33},934524,"风管穿过防火隔墙、楼板和防火墙时，穿越处风管上的防火阀、排烟防火阀两侧各（ ）m范围内的风管应采用耐火风管或风管外壁应采取防火保护措施，且耐火极限不应低于该防火分隔体的耐火极限。",[154,155,156,158],{"key":20,"text":63,"correct":22},{"key":24,"text":65,"correct":22},{"key":27,"text":157,"correct":29},"2.0",{"key":31,"text":159,"correct":22},"4.0",{"id":161,"libraryId":5,"type":15,"typeLabel":16,"stem":162,"options":163,"answer":31,"analysis":33},934525,"民用建筑的疏散门应向疏散方向开启。人数不超过（ ）人的房间且每樘门的平均疏散人数不超过（ ）人时，其门的开启方向不限。",[164,166,168,170],{"key":20,"text":165,"correct":22},"30，15",{"key":24,"text":167,"correct":22},"40，20",{"key":27,"text":169,"correct":22},"50，25",{"key":31,"text":171,"correct":29},"60，30",{"id":173,"libraryId":5,"type":15,"typeLabel":16,"stem":174,"options":175,"answer":27,"analysis":33},934526,"民用建筑和厂房的疏散门，应采用向疏散方向开启的平开门，不应采用推拉门、卷帘门、吊门、转门和折叠门。除甲、乙类生产车间外，人数不超过（ ）人且每樘门的平均疏散人数不超过30人的房间，其疏散门的开启方向不限。",[176,178,180,182],{"key":20,"text":177,"correct":22},"50",{"key":24,"text":179,"correct":22},"25",{"key":27,"text":181,"correct":29},"60",{"key":31,"text":183,"correct":22},"15",{"id":185,"libraryId":5,"type":15,"typeLabel":16,"stem":186,"options":187,"answer":27,"analysis":33},934527,"某购物中心，地下2层，建筑面积65000m2，设置南、北两个开敝的下沉式广场，下列做法中，正确的是（ ）。",[188,190,192,194],{"key":20,"text":189,"correct":22},"分隔后的购物中心不同区域通向北下沉广场开口最近边缘的水平距离为12m",{"key":24,"text":191,"correct":22},"南下沉广场上方设置雨棚，其开口面积为该空间地面面积的20%",{"key":27,"text":193,"correct":29},"南、北下沉广场各设置1部直通室外地面并满足疏散宽度指标的疏散楼梯",{"key":31,"text":195,"correct":22},"下沉式广场设置商业零售店，但不影响人员疏散",{"id":197,"libraryId":5,"type":15,"typeLabel":16,"stem":198,"options":199,"answer":20,"analysis":33},934528,"避难走道两侧应采用耐火等级不低于（ ）h的防火隔墙分隔。",[200,202,204,205],{"key":20,"text":201,"correct":29},"3.0",{"key":24,"text":203,"correct":22},"2.5",{"key":27,"text":157,"correct":22},{"key":31,"text":206,"correct":22},"1.5",{"id":208,"libraryId":5,"type":15,"typeLabel":16,"stem":209,"options":210,"answer":24,"analysis":33},934529,"高层民用建筑封闭楼梯间的门应采用（ ）。",[211,213,215,217],{"key":20,"text":212,"correct":22},"甲级防火门",{"key":24,"text":214,"correct":29},"乙级防火门",{"key":27,"text":216,"correct":22},"丙级防火门",{"key":31,"text":218,"correct":22},"能阻挡烟气的双向弹簧门",{"id":220,"libraryId":5,"type":15,"typeLabel":16,"stem":221,"options":222,"answer":20,"analysis":33},934530,"住宅建筑防烟楼梯间的防烟前室，其面积不应小于（ ）m2。",[223,225,227,229],{"key":20,"text":224,"correct":29},"4.5",{"key":24,"text":226,"correct":22},"5.0",{"key":27,"text":228,"correct":22},"5.5",{"key":31,"text":230,"correct":22},"6.0",{"id":232,"libraryId":5,"type":15,"typeLabel":16,"stem":233,"options":234,"answer":27,"analysis":33},934533,"关于室外疏散楼梯要求的说法中，下列（ ）有误。",[235,237,239,241],{"key":20,"text":236,"correct":22},"室外疏散楼梯应采取不燃材料制作",{"key":24,"text":238,"correct":22},"在楼梯周围2m内的墙面上不应设除疏散门外的其他门窗洞口",{"key":27,"text":240,"correct":29},"疏散门应正对梯段",{"key":31,"text":242,"correct":22},"楼梯段的耐火极限不应低于15min",{"id":244,"libraryId":5,"type":15,"typeLabel":16,"stem":245,"options":246,"answer":24,"analysis":33},934535,"多层建筑室外疏散楼梯的构造做法，下列组合中，完全正确的是（ ）。Ⅰ、每层出口处平台应采用钢筋混凝土构件，耐火极限不低于1小时Ⅱ、每层出口处平台和楼梯段均可采用钢构件，耐火极限不低于0.25小时Ⅲ、楼梯段的耐火极限应不低于0.25小时Ⅳ、楼梯段应采用钢筋混凝土构件，耐火极限不低于0.5小时",[247,249,250,252],{"key":20,"text":248,"correct":22},"Ⅳ、Ⅰ",{"key":24,"text":75,"correct":29},{"key":27,"text":251,"correct":22},"Ⅲ、Ⅱ",{"key":31,"text":253,"correct":22},"Ⅳ、Ⅲ",{"id":255,"libraryId":5,"type":15,"typeLabel":16,"stem":256,"options":257,"answer":20,"analysis":33},934537,"根据《建筑设计防火规范》，用作丁、戊类厂房内第二安全出口的楼梯可采用金属梯，但其净宽度不应小于（ ）m，倾斜角度不应大于450。",[258,260,261,263],{"key":20,"text":259,"correct":29},"0.9",{"key":24,"text":67,"correct":22},{"key":27,"text":262,"correct":22},"1.1",{"key":31,"text":63,"correct":22},{"id":265,"libraryId":5,"type":15,"typeLabel":16,"stem":266,"options":267,"answer":24,"analysis":33},934539,"设在变形缝处附近的防火门，应满足以下（ ）条件。Ⅰ、应设在楼层数较多的一侧；Ⅱ、应设在楼层数较少的一侧；ⅡⅠ、门开启后应跨越变形缝；Ⅳ、门开启后不应跨越变形缝",[268,270,271,272],{"key":20,"text":269,"correct":22},"Ⅰ、Ⅱ",{"key":24,"text":77,"correct":29},{"key":27,"text":79,"correct":22},{"key":31,"text":81,"correct":22},{"id":274,"libraryId":5,"type":15,"typeLabel":16,"stem":275,"options":276,"answer":20,"analysis":33},934542,"防火分隔部位设置防火卷帘时，不符合规范规定的是（ ）。",[277,279,281,283],{"key":20,"text":278,"correct":29},"除中庭外，当防火分隔部位的宽度不大于30m时，防火卷帘的宽度不应大于10m，当防火分隔部位的宽度大于30m时，防火卷帘的宽度不应大于该部位宽度的1\u002F2，且不应大于20m",{"key":24,"text":280,"correct":22},"防火卷帘应具有火灾时靠自重自动关闭功能。",{"key":27,"text":282,"correct":22},"当防火卷帘的耐火极限符合现行国家标准《门和卷帘的耐火试验方法》GB\u002FT7633有关耐火完整性和耐火隔热性的判定条件时，可不设置自动喷水灭火系统保护。",{"key":31,"text":284,"correct":22},"当防火卷帘的耐火极限仅符合现行国家标准《门和卷帘的耐火试验方法》GB\u002FT7633有关耐火完整性的判定条件时，应设置自动喷水灭火系统保护。",{"id":286,"libraryId":5,"type":15,"typeLabel":16,"stem":287,"options":288,"answer":24,"analysis":33},934544,"当建筑的屋面外保温系统采用燃烧性能为B1、B2级的保温材料时，按要求设置不燃材料制作的防护层，其厚度不小于（ ）。",[289,291,293,295],{"key":20,"text":290,"correct":22},"5mm",{"key":24,"text":292,"correct":29},"10mm",{"key":27,"text":294,"correct":22},"15mm",{"key":31,"text":296,"correct":22},"20mm",{"id":298,"libraryId":5,"type":15,"typeLabel":16,"stem":299,"options":300,"answer":27,"analysis":33},934547,"建筑的屋面外保温系统，当屋面板的耐火极限不低于（ ）h时，保温材料的燃烧性能不应低于B2级。",[301,303,305,306],{"key":20,"text":302,"correct":22},"2.00",{"key":24,"text":304,"correct":22},"1.50",{"key":27,"text":103,"correct":29},{"key":31,"text":307,"correct":22},"0.50",{"id":309,"libraryId":5,"type":15,"typeLabel":16,"stem":310,"options":311,"answer":20,"analysis":33},934549,"在对建筑外墙装饰材料进行的防火检查中，下列不符合相关规范要求的是（ ）。",[312,314,316,318],{"key":20,"text":313,"correct":29},"某星级酒店，地上20层，建筑外墙采用难燃仿花岗岩装饰板装饰",{"key":24,"text":315,"correct":22},"某综合楼，地上10层，建筑外墙采用铝扣板装饰",{"key":27,"text":317,"correct":22},"某超高层办公楼的裙房建筑外墙采用木纹金属板装饰",{"key":31,"text":319,"correct":22},"某档案馆，建筑高度40m，地上一至四层的建筑外墙采用PVC塑料护墙板装饰",{"id":321,"libraryId":5,"type":15,"typeLabel":16,"stem":322,"options":323,"answer":20,"analysis":33},934551,"某商业楼底商7层，地下2层，每层层高均为4m，建筑高度28.1m，每层建筑面积均为6000m2，地上每层划分2个防火分区。该建筑外墙采用内保温系统，其保温材料的燃烧性能为（ ）级。",[324,325,327,329],{"key":20,"text":20,"correct":29},{"key":24,"text":326,"correct":22},"B1",{"key":27,"text":328,"correct":22},"B2",{"key":31,"text":330,"correct":22},"B3",{"id":332,"libraryId":5,"type":15,"typeLabel":16,"stem":333,"options":334,"answer":31,"analysis":33},934554,"下列（ ）与基层墙体、装饰层之间有空腔的建筑外墙外保温系统的保温材料的燃烧性能可为B1级。",[335,337,339,341],{"key":20,"text":336,"correct":22},"建筑高度大于24m的人员密集场所",{"key":24,"text":338,"correct":22},"建筑高度不大于24m的人员密集场所",{"key":27,"text":340,"correct":22},"建筑高度大于24m的建筑",{"key":31,"text":342,"correct":29},"建筑高度不大于24m的除人员密集场所外的其他建筑",{"id":344,"libraryId":5,"type":15,"typeLabel":16,"stem":345,"options":346,"answer":31,"analysis":33},934556,"下列建筑宜设环形消防车道，（ ）除外。",[347,349,351,353],{"key":20,"text":348,"correct":22},"超过3000个座位的体育馆",{"key":24,"text":350,"correct":22},"超过2000个座位的会堂",{"key":27,"text":352,"correct":22},"占地面积超过3000m2的展览馆",{"key":31,"text":354,"correct":29},"占地面积超过2000m2的商店",{"id":356,"libraryId":5,"type":15,"typeLabel":16,"stem":357,"options":358,"answer":27,"analysis":33},934558,"占地面积大于（ ）m2的商店建筑、展览馆等单、多层公共建筑应设置环形消防车道。",[359,361,363,365],{"key":20,"text":360,"correct":22},"500",{"key":24,"text":362,"correct":22},"1500",{"key":27,"text":364,"correct":29},"3000",{"key":31,"text":366,"correct":22},"5000",{"id":368,"libraryId":5,"type":15,"typeLabel":16,"stem":369,"options":370,"answer":27,"analysis":33},934561,"内院或天井的短边长度大于（ ）m的建筑宜设置进入内院或天井的消防车道。",[371,373,375,377],{"key":20,"text":372,"correct":22},"120",{"key":24,"text":374,"correct":22},"150",{"key":27,"text":376,"correct":29},"24",{"key":31,"text":378,"correct":22},"220",{"id":380,"libraryId":5,"type":15,"typeLabel":16,"stem":381,"options":382,"answer":24,"analysis":33},934563,"占地面积大于30000m2的可燃材料堆场，应设置与环形消防车道相通的中间消防车道，消防车道的间距不宜大于（ ）m。",[383,385,386,387],{"key":20,"text":384,"correct":22},"180",{"key":24,"text":374,"correct":29},{"key":27,"text":372,"correct":22},{"key":31,"text":388,"correct":22},"160",{"id":390,"libraryId":5,"type":15,"typeLabel":16,"stem":391,"options":392,"answer":31,"analysis":33},934565,"消防车登高操作场地是消防灭火救援的重要设施。下列关于消防车登高操作场地设置的说法中，错误的是（ ）。",[393,395,397,399],{"key":20,"text":394,"correct":22},"高层建筑应至少沿一个长边或周边长度的1\u002F4且不小于一个长边长度的底边连续布置消防车登高操作场地",{"key":24,"text":396,"correct":22},"消防车登高操作场地靠建筑外墙一侧的边缘距离建筑外墙不应大于10m",{"key":27,"text":398,"correct":22},"消防车登高操作场地的坡度不宜大于3%",{"key":31,"text":400,"correct":29},"高层建筑的消防车登高面不应布置裙房",{"id":402,"libraryId":5,"type":15,"typeLabel":16,"stem":403,"options":404,"answer":31,"analysis":33},934567,"为满足登高消防车火灾扑救作业的要求，高层民用建筑底部应留出足够长度的扑救面，具体应满足（ ）要求。Ⅰ、扑救面长度不小于高层民用建筑主体的一条长边或1\u002F3周长：Ⅱ、扑救面长度不小于高层民用建筑主体的一条长边或1\u002F4周长；Ⅲ、扑救面范围内不应布置高度大于5m，进深大于4m的裙房；Ⅳ、扑救面范围内不应布置进深大于4m的裙房",[405,406,407,408],{"key":20,"text":269,"correct":22},{"key":24,"text":77,"correct":22},{"key":27,"text":79,"correct":22},{"key":31,"text":81,"correct":29},{"id":410,"libraryId":5,"type":15,"typeLabel":16,"stem":411,"options":412,"answer":27,"analysis":33},934570,"建筑高度不大于（ ）m的建筑，连续布置消防车登高操作场地确有困难时，可间隔布置，但间隔距离不宜大于30m，且消防车登高操作场地的总长度仍应符合上述规定。",[413,414,416,417],{"key":20,"text":376,"correct":22},{"key":24,"text":415,"correct":22},"27",{"key":27,"text":177,"correct":29},{"key":31,"text":418,"correct":22},"54",{"id":420,"libraryId":5,"type":15,"typeLabel":16,"stem":421,"options":422,"answer":31,"analysis":33},934572,"消防电梯前室在首层设通道通向出口，其通道的长度不应大于（ ）。",[423,425,427,429],{"key":20,"text":424,"correct":22},"10m",{"key":24,"text":426,"correct":22},"14m",{"key":27,"text":428,"correct":22},"20m",{"key":31,"text":430,"correct":29},"30m",{"id":432,"libraryId":5,"type":15,"typeLabel":16,"stem":433,"options":434,"answer":27,"analysis":33},934574,"消防电梯的井底应设置排水设施，排水井的容量不应小于（ ）m3，排水泵的排水量不应小于（ ）1\u002Fs。消防电梯间前室的门口宜设置挡水设施。",[435,437,439,441],{"key":20,"text":436,"correct":22},"2，15",{"key":24,"text":438,"correct":22},"3，5",{"key":27,"text":440,"correct":29},"2，10",{"key":31,"text":442,"correct":22},"3，15",{"id":444,"libraryId":5,"type":15,"typeLabel":16,"stem":445,"options":446,"answer":20,"analysis":33},934577,"消防电梯的载重量及行驶速度。为了满足消防扑救的需要，消防电梯应选用较大的载重量，一般不应小于（ ）kg，消防电梯的行驶速度从首层至顶层的运行时间不宜大于（ ）min。",[447,449,451,453],{"key":20,"text":448,"correct":29},"800，1",{"key":24,"text":450,"correct":22},"800，60",{"key":27,"text":452,"correct":22},"600，1",{"key":31,"text":454,"correct":22},"600，60",{"id":456,"libraryId":5,"type":15,"typeLabel":16,"stem":457,"options":458,"answer":27,"analysis":33},934579,"消防电梯井和其他相邻电梯井之间的个墙上开门时，应采用的防火门和消防电梯间前室上应采用的防火门（ ）。",[459,461,463,465],{"key":20,"text":460,"correct":22},"均为甲级防火门",{"key":24,"text":462,"correct":22},"均为乙级防火门",{"key":27,"text":464,"correct":29},"前者为甲级防火门，后者为乙级防火门",{"key":31,"text":466,"correct":22},"前者为乙级防火门，后者为甲级防火门",{"id":468,"libraryId":5,"type":15,"typeLabel":16,"stem":469,"options":470,"answer":31,"analysis":33},934581,"下列关于设备用房布置的叙述中，错误的是（ ）。",[471,473,475,477],{"key":20,"text":472,"correct":22},"锅炉房应设置在首层或地下一层",{"key":24,"text":474,"correct":22},"柴油发电机房宣布置在地下一、二层",{"key":27,"text":476,"correct":22},"消防控制室应设在首层或地下一层靠外墙部位",{"key":31,"text":478,"correct":29},"消防水泵房可以设在地下室内地面与室外出入口地坪高差不大于10m的地下三层",{"id":480,"libraryId":5,"type":15,"typeLabel":16,"stem":481,"options":482,"answer":31,"analysis":33},934583,"下列关于建筑平面布置的叙述中，不正确的是（ ）。",[483,485,487,489],{"key":20,"text":484,"correct":22},"会议厅宜布置在一二三层",{"key":24,"text":486,"correct":22},"耐火等级为三级的会议厅宜布置在首层、二层",{"key":27,"text":488,"correct":22},"消防控制室应设在首层或地下一层",{"key":31,"text":490,"correct":29},"消防水泵房不应设在地下二层",{"id":492,"libraryId":5,"type":15,"typeLabel":16,"stem":493,"options":494,"answer":31,"analysis":33},934586,"下列有关高层民用建筑防火分区的规定，（ ）是正确的。",[495,497,499,501],{"key":20,"text":496,"correct":22},"高度小于50m的病房楼，按国家规范要求设置了灭火系统，防火分区允许最大建筑面积1500m2",{"key":24,"text":498,"correct":22},"高度小于50m的科研楼，按国家规范要求设置了灭火系统，防火分区允许最大建筑面积1000m2",{"key":27,"text":500,"correct":22},"高度为80m的宾馆，设有火灾自动报警系统和自动灭火系统，防火分区允许最大建筑面积2500m2",{"key":31,"text":502,"correct":29},"高度为45m的办公楼的地下室（后勤用房），按国家规范要求设置了灭火系统，防火分区允许最大建筑面积1000m2",{"id":504,"libraryId":5,"type":15,"typeLabel":16,"stem":505,"options":506,"answer":31,"analysis":33},934588,"根据现行国家消防技术标准，下列净化或输送有爆炸危险粉尘和碎屑的设施上，不需要设置泄压装置的是（ ）。（2016-能力）",[507,509,511,513],{"key":20,"text":508,"correct":22},"除尘器",{"key":24,"text":510,"correct":22},"过滤器",{"key":27,"text":512,"correct":22},"管道",{"key":31,"text":514,"correct":29},"风机",{"id":516,"libraryId":5,"type":15,"typeLabel":16,"stem":517,"options":518,"answer":20,"analysis":33},934590,"某住宅建筑自然层数为11层，其中底部为室内高度2.2m的自行车库，屋顶上突出的局部用房占屋面面积的1\u002F2，则该建筑层数为（ ）。",[519,521,523,525],{"key":20,"text":520,"correct":29},"10",{"key":24,"text":522,"correct":22},"11",{"key":27,"text":524,"correct":22},"12",{"key":31,"text":526,"correct":22},"13",{"id":528,"libraryId":5,"type":15,"typeLabel":16,"stem":529,"options":530,"answer":31,"analysis":33},934592,"二级耐火等级建筑的吊顶采用难燃材料制作时，其耐火极限不应低于（ ），采用不燃材料制作时，其耐火极限（ ）。",[531,533,535,537],{"key":20,"text":532,"correct":22},"1.00h，不低于0.50h",{"key":24,"text":534,"correct":22},"0.50，不低于0.25h",{"key":27,"text":536,"correct":22},"0.50，不限",{"key":31,"text":538,"correct":29},"0.25，不限",{"id":540,"libraryId":5,"type":15,"typeLabel":16,"stem":541,"options":542,"answer":31,"analysis":33},934594,"耐火等级为一级的厂房和仓库建筑构件的疏散走道两侧的隔墙，其耐火极限为（ ）h。",[543,545,547,548],{"key":20,"text":544,"correct":22},"3.00",{"key":24,"text":546,"correct":22},"2.50",{"key":27,"text":302,"correct":22},{"key":31,"text":103,"correct":29},{"id":550,"libraryId":5,"type":15,"typeLabel":16,"stem":551,"options":552,"answer":24,"analysis":33},934596,"建筑高度为20m的乙炔站与四级耐火等级多层民用建筑的防火间距不应小于（ ）。",[553,555,556,558],{"key":20,"text":554,"correct":22},"30",{"key":24,"text":179,"correct":29},{"key":27,"text":557,"correct":22},"20",{"key":31,"text":559,"correct":22},"16",{"id":561,"libraryId":5,"type":15,"typeLabel":16,"stem":562,"options":563,"answer":31,"analysis":33},934598,"非高层民用建筑，未设置自动喷淋系统，耐火等级为一、二级时，其防火分区允许的最大建筑面积应是（ ）。",[564,566,568,570],{"key":20,"text":565,"correct":22},"1000m2",{"key":24,"text":567,"correct":22},"1500m2",{"key":27,"text":569,"correct":22},"2000m2",{"key":31,"text":571,"correct":29},"2500m2",{"id":573,"libraryId":5,"type":15,"typeLabel":16,"stem":574,"options":575,"answer":27,"analysis":33},934600,"二类高层民用建筑每个防火分区的建筑面积应不大于（ ）。",[576,578,579,580],{"key":20,"text":577,"correct":22},"500m2",{"key":24,"text":565,"correct":22},{"key":27,"text":567,"correct":29},{"key":31,"text":569,"correct":22},{"id":582,"libraryId":5,"type":15,"typeLabel":16,"stem":583,"options":584,"answer":27,"analysis":33},934602,"一座5层办公楼，每层3.8m，耐火等级为二级，每层建筑积为7000m2，如果不设自动灭火设备，每层应设（ ）防火分区。",[585,587,589,591],{"key":20,"text":586,"correct":22},"1个",{"key":24,"text":588,"correct":22},"2个",{"key":27,"text":590,"correct":29},"3个",{"key":31,"text":592,"correct":22},"4个",[594,597,600,603,606,609],{"id":15,"name":595,"category":7,"favorite":596},"领导干部任职前廉政法规知识测试题",92,{"id":598,"name":599,"category":7,"favorite":15},595,"建筑结构与设备",{"id":601,"name":602,"category":7,"favorite":15},715,"招标采购专业知识与法律法规",{"id":604,"name":605,"category":7,"favorite":15},848,"市政方向-通用基础",{"id":607,"name":608,"category":7,"favorite":8},534,"BIM工程师",{"id":610,"name":608,"category":7,"favorite":8},535]