[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"lib-604-20":3},{"library":4,"page":9,"limit":10,"total":11,"questions":12,"related":619},{"id":5,"name":6,"category":7,"favorite":8},604,"消防安全技术实务(一级)","建筑工程",0,20,50,2960,[13,34,46,58,70,81,92,104,116,128,140,151,162,174,184,196,205,217,229,241,253,265,277,289,301,313,325,337,345,357,369,381,392,401,413,425,434,446,458,468,479,487,505,520,535,550,565,580,595,607],{"id":14,"libraryId":5,"type":15,"typeLabel":16,"stem":17,"options":18,"answer":27,"analysis":33},932650,1,"单选题","某42层住宅楼，每个防火分区的最大允许建筑面积不应大于（ ）m2。",[19,23,26,30],{"key":20,"text":21,"correct":22},"A","1500",false,{"key":24,"text":25,"correct":22},"B","2500",{"key":27,"text":28,"correct":29},"C","3000",true,{"key":31,"text":32,"correct":22},"D","5000","",{"id":35,"libraryId":5,"type":15,"typeLabel":16,"stem":36,"options":37,"answer":27,"analysis":33},932651,"某综合楼，共10层，一至三层为商场，三层以上为住宅，当建筑内全部设置自动喷水灭火系统时，住宅与非住宅相接处上下层开口之间应设置挑出宽度不小于（ ）m的防火挑檐。",[38,40,42,44],{"key":20,"text":39,"correct":22},"0．5",{"key":24,"text":41,"correct":22},"0．8",{"key":27,"text":43,"correct":29},"1．0",{"key":31,"text":45,"correct":22},"1．2",{"id":47,"libraryId":5,"type":15,"typeLabel":16,"stem":48,"options":49,"answer":20,"analysis":33},932652,"下列关于防火墙的做法中，错误的是（ ）。",[50,52,54,56],{"key":20,"text":51,"correct":29},"输送柴油（闪点高于60℃）的管道穿过防火墙时，穿墙管道四周缝隙采用防火堵料严密封堵",{"key":24,"text":53,"correct":22},"防火墙上设置常开的甲级防火门，发生火灾时能够自行关闭",{"key":27,"text":55,"correct":22},"高层厂房屋顶承重结构和屋面板的耐火极限低于1．00h时，防火墙应高出屋面0．5m以上",{"key":31,"text":57,"correct":22},"建筑外墙为难燃性墙体时，防火墙应凸出墙的外表面0．4m以上",{"id":59,"libraryId":5,"type":15,"typeLabel":16,"stem":60,"options":61,"answer":24,"analysis":33},932653,"某耐火等级为一级的丙类厂房，由于需要进出大型设备，防火分区处的部分防火墙用防火卷帘替代，则防火卷帘的耐火极限不应低于（ ）h。",[62,64,66,68],{"key":20,"text":63,"correct":22},"2．50",{"key":24,"text":65,"correct":29},"3．00",{"key":27,"text":67,"correct":22},"3．50",{"key":31,"text":69,"correct":22},"4．00",{"id":71,"libraryId":5,"type":15,"typeLabel":16,"stem":72,"options":73,"answer":27,"analysis":33},932654,"某四级耐火等级的单层戊类厂房，净空高度为6．2m，建筑面积为2000m2，厂房内未设置自动喷水灭火系统。当设置排烟系统时，防烟分区的最大允许面积不应大于（ ）m2。",[74,76,78,79],{"key":20,"text":75,"correct":22},"500",{"key":24,"text":77,"correct":22},"1000",{"key":27,"text":21,"correct":29},{"key":31,"text":80,"correct":22},"2000",{"id":82,"libraryId":5,"type":15,"typeLabel":16,"stem":83,"options":84,"answer":20,"analysis":33},932655,"当采用建筑横梁作为防烟分区分隔设施时，其高度应大于（ ）m。",[85,86,88,90],{"key":20,"text":39,"correct":29},{"key":24,"text":87,"correct":22},"1",{"key":27,"text":89,"correct":22},"1．5",{"key":31,"text":91,"correct":22},"2",{"id":93,"libraryId":5,"type":15,"typeLabel":16,"stem":94,"options":95,"answer":27,"analysis":33},932656,"下列做法中正确的是（ ）。",[96,98,100,102],{"key":20,"text":97,"correct":22},"某教学建筑，采用三级耐火等级建筑，建筑层数为3层",{"key":24,"text":99,"correct":22},"某成品纸仓库，建筑面积为1000m2，其中50m2用来储存油纸，仓库设置在地下一层，每个防火分区建筑面积为300m2",{"key":27,"text":101,"correct":29},"某多层办公楼，每层建筑面积为3600m2，楼板采用耐火极限为0．5h的不燃材料制作，每层划分为3个防火分区",{"key":31,"text":103,"correct":22},"某商店建筑，采用四级耐火等级建筑，建筑层数为2层",{"id":105,"libraryId":5,"type":15,"typeLabel":16,"stem":106,"options":107,"answer":24,"analysis":33},932657,"下列关于厂房、仓库防火分隔的说法，不正确的是（ ）。",[108,110,112,114],{"key":20,"text":109,"correct":22},"二级耐火等级的赛璐珞厂房划分防火分区时，应采用耐火极限不低于4．00h的防火墙分隔",{"key":24,"text":111,"correct":29},"手机等电子设备储存仓库，耐火等级为二级，应采用不设门、窗、洞口且耐火极限不低于3．00h的防火墙分隔",{"key":27,"text":113,"correct":22},"单层煤油灌装车间，耐火等级为二级，建筑面积为2500m2，确有困难时，可采用符合规范要求的防火卷帘划分防火分区",{"key":31,"text":115,"correct":22},"青花瓷存储仓库，采用防火墙划分防火分区时，可在防火墙上设置为方便通行4m×4m的防火卷帘",{"id":117,"libraryId":5,"type":15,"typeLabel":16,"stem":118,"options":119,"answer":27,"analysis":33},932658,"某单层商店，划分三个防火分区，分别为 A、 B、 C，A与B防火分隔部位宽度为30m，A与C之间防火分隔部位宽度为45m，则A防火分区所用防火卷帘的总宽度不应大于（ ）m。",[120,122,124,126],{"key":20,"text":121,"correct":22},"10",{"key":24,"text":123,"correct":22},"20",{"key":27,"text":125,"correct":29},"25",{"key":31,"text":127,"correct":22},"30",{"id":129,"libraryId":5,"type":15,"typeLabel":16,"stem":130,"options":131,"answer":27,"analysis":33},932659,"某地上酚醛泡沫塑料加工厂房，厂房内设置了自动灭火系统，该厂房每个防火分区的最大允许建筑面积（ ）。",[132,134,136,138],{"key":20,"text":133,"correct":22},"不应大于4000m2",{"key":24,"text":135,"correct":22},"不应大于5000m2",{"key":27,"text":137,"correct":29},"不限",{"key":31,"text":139,"correct":22},"不应大于8000m2",{"id":141,"libraryId":5,"type":15,"typeLabel":16,"stem":142,"options":143,"answer":24,"analysis":33},932660,"某二级耐火等级的多层丙类厂房，其中一个防火分区局部设置了自动灭火系统，设置自动灭火系统的总面积为1000m2，则该防火分区的最大允许建筑面积为（ ）m2。",[144,146,148,149],{"key":20,"text":145,"correct":22},"4000",{"key":24,"text":147,"correct":29},"4500",{"key":27,"text":32,"correct":22},{"key":31,"text":150,"correct":22},"6000",{"id":152,"libraryId":5,"type":15,"typeLabel":16,"stem":153,"options":154,"answer":27,"analysis":33},932661,"某二级耐火等级泡沫塑料发泡车间，其建筑层数（ ）。",[155,157,159,160],{"key":20,"text":156,"correct":22},"最多为2层",{"key":24,"text":158,"correct":22},"最多为6层",{"key":27,"text":137,"correct":29},{"key":31,"text":161,"correct":22},"最多为1层",{"id":163,"libraryId":5,"type":15,"typeLabel":16,"stem":164,"options":165,"answer":20,"analysis":33},932662,"某单层金属制品抛光厂房，建筑面积8000m2，耐火等级为二级，未设置自动灭火系统和火灾自动报警系统，则下列做法中正确的是（ ）。",[166,168,170,172],{"key":20,"text":167,"correct":29},"将该车间划分为一个防火分区，并全部设置自动灭火系统",{"key":24,"text":169,"correct":22},"因生产工艺要求，采用仅满足耐火隔热性的防火卷帘将厂房划分成两个防火分区，每个防火分区面积不大于4000m2",{"key":27,"text":171,"correct":22},"对该车间进行消防设施改造，安装火灾自动报警系统后，可将该车间划分为一个防火分区",{"key":31,"text":173,"correct":22},"对该车间采用防火墙进行分隔，其中最大一个防火分区建筑面积为6000m2",{"id":175,"libraryId":5,"type":15,"typeLabel":16,"stem":176,"options":177,"answer":24,"analysis":33},932663,"某单层硝化棉仓库，建筑面积160m2，设置了雨淋自动喷水灭火系统，最少应划分成（ ）个防火分区。",[178,179,180,182],{"key":20,"text":87,"correct":22},{"key":24,"text":91,"correct":29},{"key":27,"text":181,"correct":22},"3",{"key":31,"text":183,"correct":22},"4",{"id":185,"libraryId":5,"type":15,"typeLabel":16,"stem":186,"options":187,"answer":31,"analysis":33},932664,"下列仓库可以设置在地下的是（ ）。",[188,190,192,194],{"key":20,"text":189,"correct":22},"某一级耐火等级的甲苯仓库",{"key":24,"text":191,"correct":22},"某二级耐火等级的油纸制品仓库",{"key":27,"text":193,"correct":22},"某三级耐火等级的水泥刨花板制品仓库",{"key":31,"text":195,"correct":29},"某二级耐火等级的天然橡胶制品仓库",{"id":197,"libraryId":5,"type":15,"typeLabel":16,"stem":198,"options":199,"answer":24,"analysis":33},932665,"某办公楼，主体建筑高度45m，地上12层，裙房2层，裙房与高层建筑主体之间设置防火墙，在未设置自动灭火系统的情况下，裙房的一个防火分区最大允许建筑面积为（ ）m2。",[200,201,202,204],{"key":20,"text":21,"correct":22},{"key":24,"text":25,"correct":29},{"key":27,"text":203,"correct":22},"1200",{"key":31,"text":28,"correct":22},{"id":206,"libraryId":5,"type":15,"typeLabel":16,"stem":207,"options":208,"answer":27,"analysis":33},932666,"某高层商业中心，建筑高度54m，高层建筑主体与裙房采用防火墙分隔，主体建筑地上12层，地下2层，建筑均采用不燃、难燃材料装修。地下一层为大型商场，地下二层为大型商场和设备用房，地上楼层为展览厅、影院、餐厅等。则下列关于建筑防火分区面积的说法，正确的是（ ）。",[209,211,213,215],{"key":20,"text":210,"correct":22},"地下一层大型商场营业厅每个防火分区建筑面积最大为1000m2",{"key":24,"text":212,"correct":22},"设置在主楼首层的展览厅每个防火分区的建筑面积为10000m2",{"key":27,"text":214,"correct":29},"设置在裙房中的电影院每个防火分区的建筑面积为5000m2",{"key":31,"text":216,"correct":22},"地下二层设备用房每个防火分区的建筑面积最大为1000m2",{"id":218,"libraryId":5,"type":15,"typeLabel":16,"stem":219,"options":220,"answer":31,"analysis":33},932667,"总建筑面积为32000m2的地下商店，采用无门、窗、洞口的防火墙且耐火极限不低于2．0h的楼板分隔为多个建筑面积不大于20000m2的区域。相邻区域确需局部连通时，不可以采用的是（ ）。",[221,223,225,227],{"key":20,"text":222,"correct":22},"下沉式广场",{"key":24,"text":224,"correct":22},"避难走道",{"key":27,"text":226,"correct":22},"防烟楼梯间",{"key":31,"text":228,"correct":29},"疏散走道",{"id":230,"libraryId":5,"type":15,"typeLabel":16,"stem":231,"options":232,"answer":27,"analysis":33},932668,"建筑内的各种设备用房是保证建筑功能实现的重要场所，其与建筑物的防火分隔显得尤为重要，下面关于设备用房防火分隔的说法不正确的是（ ）。",[233,235,237,239],{"key":20,"text":234,"correct":22},"附设在建筑内的变配电房采用耐火极限为2．00h的防火隔墙和1．50h的楼板与其他部位分隔，开向建筑内的门采用甲级防火门",{"key":24,"text":236,"correct":22},"布置在民用建筑内的锅炉房与其他部位之间采用耐火极限为2．00h的防火隔墙和1．50h的楼板与其他部位分隔，隔墙上的门采用甲级防火门",{"key":27,"text":238,"correct":29},"附设在建筑内的通风空调机房采用耐火极限为2．00h的防火隔墙和1．50h的楼板与其他部位分隔，开向建筑内的门采用乙级防火门",{"key":31,"text":240,"correct":22},"布置在民用建筑内的柴油发电机房与其他部位之间采用耐火极限为2．00h的防火隔墙和1．50h的楼板与其他部位分隔，隔墙上的门采用甲级防火门",{"id":242,"libraryId":5,"type":15,"typeLabel":16,"stem":243,"options":244,"answer":20,"analysis":33},932669,"建筑内的管道和管道井是火灾烟气和火灾蔓延的途径，下列对建筑内各种井道的说法正确的是（ ）。",[245,247,249,251],{"key":20,"text":246,"correct":29},"电缆井墙壁上的检查门采用丙级防火门",{"key":24,"text":248,"correct":22},"电梯井的井壁耐火极限为1．00h",{"key":27,"text":250,"correct":22},"建筑内的配电线路通过电梯井敷设",{"key":31,"text":252,"correct":22},"管道井在每层用耐火极限为1．00h的不燃材料对缝隙进行封堵",{"id":254,"libraryId":5,"type":15,"typeLabel":16,"stem":255,"options":256,"answer":27,"analysis":33},932670,"某商业建筑，地上3层，拟改建为超市，需要对内部原有结构进行改造，则下列关于防火分隔的做法中，正确的是（ ）。",[257,259,261,263],{"key":20,"text":258,"correct":22},"为缩短所筑内部防火墙长度，将该防火墙设在建筑内部转角处，两侧外墙上有相距2．0m的普通门窗",{"key":24,"text":260,"correct":22},"内部一较窄部位采用防火墙进行分隔，为便于通行，在墙上设置了乙级防火门，可以保证在关闭后能从任一侧手动开启",{"key":27,"text":262,"correct":29},"内部一宽度为30m的分隔部位，设置总宽度为8m的防火卷帘",{"key":31,"text":264,"correct":22},"由于整个建筑物体量大，其内部设有变形缝，在变形缝处设置的防火门常闭，开启后防火门可以跨越变形缝",{"id":266,"libraryId":5,"type":15,"typeLabel":16,"stem":267,"options":268,"answer":31,"analysis":33},932671,"下列不能用于划分防烟分区的构件是（ ）。",[269,271,273,275],{"key":20,"text":270,"correct":22},"挡烟垂壁",{"key":24,"text":272,"correct":22},"防火卷帘",{"key":27,"text":274,"correct":22},"隔墙",{"key":31,"text":276,"correct":29},"高度不小于空间净高的10％的建筑横梁",{"id":278,"libraryId":5,"type":15,"typeLabel":16,"stem":279,"options":280,"answer":27,"analysis":33},932672,"下列关于防火阀设置的做法，不正确的是（ ）。",[281,283,285,287],{"key":20,"text":282,"correct":22},"某27m的公共建筑浴室的竖向排风管，采取防止回流措施，并在支管上设置公称动作温度为70℃的防火阀",{"key":24,"text":284,"correct":22},"某32m的综合楼卫生间的竖向排风管，采取防止回流措施，并在支管上设置公称动作温度为70℃的防火阀",{"key":27,"text":286,"correct":29},"某54m的商业建筑厨房的排油烟管道，采取防止回流措施，并在支管上设置公称动作温度为70℃的防火阀",{"key":31,"text":288,"correct":22},"排烟防火阀应采用280℃温度熔断器自动关闭",{"id":290,"libraryId":5,"type":15,"typeLabel":16,"stem":291,"options":292,"answer":27,"analysis":33},932673,"防火墙是防止火灾蔓延至相邻建筑或相邻水平防火分区且耐火极限不低于3．00h的不燃性墙体，是防火分区中常见的固定式防火分隔构件。下列关于防火墙的设置要求，错误的是（ ）。",[293,295,297,299],{"key":20,"text":294,"correct":22},"防火墙上不应开设门、窗、洞口，确需开设时，应设置不可开启或火灾时能自动关闭的甲级防火门、窗",{"key":24,"text":296,"correct":22},"可燃气体和甲、乙、丙类液体的管道严禁穿过防火墙，防火墙内不应设置排气道",{"key":27,"text":298,"correct":29},"仓库内的防火分区之间必须采用防火墙分隔，甲、乙类仓库内防火分区之间的防火墙不应开设门、窗、洞口，需在防火墙上开窗时，应采用甲级防火窗",{"key":31,"text":300,"correct":22},"防火墙的构造应能在防火墙任意一侧的屋架、梁、楼板等受到火灾的影响而破坏时，不会导致防火墙倒塌",{"id":302,"libraryId":5,"type":15,"typeLabel":16,"stem":303,"options":304,"answer":20,"analysis":33},932674,"下列排烟管道的部位，可不设置排烟防火阀的是（）。",[305,307,309,311],{"key":20,"text":306,"correct":29},"垂直风管与每层水平风管交接处的垂直风管上",{"key":24,"text":308,"correct":22},"排烟风机入口处",{"key":27,"text":310,"correct":22},"一个排烟系统负担多个防烟分区的排烟支管上",{"key":31,"text":312,"correct":22},"穿越防火分区处",{"id":314,"libraryId":5,"type":15,"typeLabel":16,"stem":315,"options":316,"answer":24,"analysis":33},932675,"防烟分区是在建筑内部采用挡烟设施分隔而成，能在一定时间内防止火灾烟气向同一防火分区的其余部分蔓延的局部空间。一般情况下，防烟分区的长边不应大于60m，当室内高度超过6m且具有对流条件时，防烟分区的长边不应大于（ ）m。",[317,319,321,323],{"key":20,"text":318,"correct":22},"70",{"key":24,"text":320,"correct":29},"75",{"key":27,"text":322,"correct":22},"80",{"key":31,"text":324,"correct":22},"85",{"id":326,"libraryId":5,"type":15,"typeLabel":16,"stem":327,"options":328,"answer":31,"analysis":33},932676,"某商业综合体，地下2层为商场，层高4m，每层建筑面积12000m2，建筑内部装修材料全部采用不燃材料，按照现行国家消防技术标准设置了消防设施。下列关于该商场防火设计的做法，不符合规范要求的是（ ）。",[329,331,333,335],{"key":20,"text":330,"correct":22},"该商场每层划分为6个防火分区",{"key":24,"text":332,"correct":22},"地下一层与地下二层之间采用耐火极限为2．00h的楼板将商场分隔为两部分",{"key":27,"text":334,"correct":22},"地下二层防火分区之间采用耐火极限为3．00h的防火卷帘分隔",{"key":31,"text":336,"correct":29},"上下层之间采用防烟楼梯间进行局部连通，楼梯间的门采用乙级防火门",{"id":338,"libraryId":5,"type":15,"typeLabel":16,"stem":339,"options":340,"answer":24,"analysis":33},932677,"某服装厂房，地上4层，层高6．5m，每层建筑面积为2600m2，室内净空高度为6m，厂房内设置了机械排烟系统，则该厂房内一个防烟分区的最大允许面积不应大于（）。",[341,342,343,344],{"key":20,"text":75,"correct":22},{"key":24,"text":77,"correct":29},{"key":27,"text":80,"correct":22},{"key":31,"text":25,"correct":22},{"id":346,"libraryId":5,"type":15,"typeLabel":16,"stem":347,"options":348,"answer":27,"analysis":33},932678,"步行街的顶棚下檐距地面的高度不应小于6.0m，顶棚应设置自然排烟设施并宜采用常开式的排烟口, 且自然排烟口的有效面积不应小于步行街地面面积的（ ）。",[349,351,353,355],{"key":20,"text":350,"correct":22},"35%",{"key":24,"text":352,"correct":22},"30%",{"key":27,"text":354,"correct":29},"25%",{"key":31,"text":356,"correct":22},"20%",{"id":358,"libraryId":5,"type":15,"typeLabel":16,"stem":359,"options":360,"answer":24,"analysis":33},932679,"某办公楼建筑，地上 15 层，地下 2 层，设置有裙房。该办公楼室外地坪 标高为-0.600m，屋顶为平屋面，面层标高为 49.80m，女儿墙高度为 1.20m。裙房共 4 层，每层高度均为 4.5m。该办公楼主体结构与裙房之间设置有防火墙，裙 房的一、二层设置有大型购物超市，三、四层均为歌舞娱乐场所。地下一层为各种 消防设备用房，地下二层为汽车库。该建筑按相关消防要求全部设置自动喷水灭火 系统和火灾自动报警系统等，并采用不燃性材料进行内部装修，下列关于防火分区划分的做法中，错误的是（ ）。",[361,363,365,367],{"key":20,"text":362,"correct":22},"该办公楼主体结构中，一个防火分区的建筑面积为 2500 ㎡",{"key":24,"text":364,"correct":29},"裙房中大型超市的一个防火分区的建筑面积为 9000 ㎡",{"key":27,"text":366,"correct":22},"地下一层设备用房的一个防火分区的建筑面积为 1900 ㎡",{"key":31,"text":368,"correct":22},"地下二层的汽车库一个防火分区的建筑面积为 3990 ㎡",{"id":370,"libraryId":5,"type":15,"typeLabel":16,"stem":371,"options":372,"answer":20,"analysis":33},932680,"总建筑面积大于 20000 ㎡的地下或半地下商店，应采用无门、窗、洞口的防火墙、耐火极限不低于 2.00h的楼板分隔为多个建筑面积不大于 20000 ㎡的区域；相邻区域确需局部水平或竖向连通时，可采用符合下列（ ）条件的防烟楼梯间进行连通。",[373,375,377,379],{"key":20,"text":374,"correct":29},"防烟楼梯间及其前室的门均应采用甲级防火门",{"key":24,"text":376,"correct":22},"防烟楼梯间的门应采用甲级防火门,其前室的门可采用乙级防火门",{"key":27,"text":378,"correct":22},"防烟楼梯间及其前室的门均可采用乙级防火门",{"key":31,"text":380,"correct":22},"防烟楼梯间的门可采用乙级防火门,其前室的门应采用甲级防火门",{"id":382,"libraryId":5,"type":15,"typeLabel":16,"stem":383,"options":384,"answer":31,"analysis":33},932681,"排烟防火阀是安装在排烟系统管道上起隔烟、阻火作用的阀门，当管道内的烟气达到（ ）℃时排烟阀门自动关闭。",[385,386,388,390],{"key":20,"text":318,"correct":22},{"key":24,"text":387,"correct":22},"150",{"key":27,"text":389,"correct":22},"250",{"key":31,"text":391,"correct":29},"280",{"id":393,"libraryId":5,"type":15,"typeLabel":16,"stem":394,"options":395,"answer":27,"analysis":33},932682,"建筑物内的防火墙不应设在转角处，如设在转角附近，内转角两侧上的门、窗、洞口之间最近的水平距离不应小于（ ）m。",[396,397,399,400],{"key":20,"text":121,"correct":22},{"key":24,"text":398,"correct":22},"6",{"key":27,"text":183,"correct":29},{"key":31,"text":91,"correct":22},{"id":402,"libraryId":5,"type":15,"typeLabel":16,"stem":403,"options":404,"answer":24,"analysis":33},932683,"为了保证安全，除中庭外，当防火分隔部位的宽度不大于30m时，防火卷帘的宽度不应大于（ ）。",[405,407,409,411],{"key":20,"text":406,"correct":22},"5m",{"key":24,"text":408,"correct":29},"10m",{"key":27,"text":410,"correct":22},"15m",{"key":31,"text":412,"correct":22},"20m",{"id":414,"libraryId":5,"type":15,"typeLabel":16,"stem":415,"options":416,"answer":20,"analysis":33},932684,"无特殊情况下，当建筑内设置自动灭火系统时，防火分区最大允许建筑面积可按相关规定增加（ ）。",[417,419,421,423],{"key":20,"text":418,"correct":29},"1倍",{"key":24,"text":420,"correct":22},"2倍",{"key":27,"text":422,"correct":22},"1000m2",{"key":31,"text":424,"correct":22},"2000m2",{"id":426,"libraryId":5,"type":15,"typeLabel":16,"stem":427,"options":428,"answer":31,"analysis":33},932685,"二级耐火等级的乙类厂房建筑层数最多不超过（ ）层。",[429,430,431,433],{"key":20,"text":91,"correct":22},{"key":24,"text":181,"correct":22},{"key":27,"text":432,"correct":22},"5",{"key":31,"text":398,"correct":29},{"id":435,"libraryId":5,"type":15,"typeLabel":16,"stem":436,"options":437,"answer":27,"analysis":33},932686,"乙级防火门是指（）的防火门。",[438,440,442,444],{"key":20,"text":439,"correct":22},"耐火完整性不小于1.50h",{"key":24,"text":441,"correct":22},"耐火隔燃性不小于1.50h",{"key":27,"text":443,"correct":29},"耐火完整性和耐火隔热性均不小于1.00h",{"key":31,"text":445,"correct":22},"耐火完整性和耐火隔热性均不小于1.50h",{"id":447,"libraryId":5,"type":15,"typeLabel":16,"stem":448,"options":449,"answer":20,"analysis":33},932687,"某高层商场外墙采用玻璃幕墙，1-5层设有中庭，消防设施符合国家规定最低标准，下列建筑防火设计符合要求的是（）",[450,452,454,456],{"key":20,"text":451,"correct":29},"中庭四周采用防火卷帘加水幕冷却保护的分隔方式，耐火极限不小于3.0h",{"key":24,"text":453,"correct":22},"中庭设有自动喷水灭火系统和火灾自动报警系统，顶面和地面应采用不燃材料装修，设有机械排烟系统",{"key":27,"text":455,"correct":22},"该建筑每层楼板外檐处未设置实体墙，玻璃幕墙应采用耐火极限不低于1.0h的防火玻璃",{"key":31,"text":457,"correct":22},"建筑外墙上、下层开口之间应设置挑出宽度不小于1.2m的防护挑檐",{"id":459,"libraryId":5,"type":15,"typeLabel":16,"stem":460,"options":461,"answer":24,"analysis":33},932688,"二级耐火等级的面粉成品仓库设置在地下时，未设置自动喷水灭火系统，每个防火分区的最大允许建筑面积不应大于（ ）m2。",[462,463,465,467],{"key":20,"text":387,"correct":22},{"key":24,"text":464,"correct":29},"300",{"key":27,"text":466,"correct":22},"600",{"key":31,"text":77,"correct":22},{"id":469,"libraryId":5,"type":15,"typeLabel":16,"stem":470,"options":471,"answer":27,"analysis":33},932689,"某单层木结构建筑中防火墙间的每层最大允许建筑面积为（ ）㎡。",[472,473,475,477],{"key":20,"text":466,"correct":22},{"key":24,"text":474,"correct":22},"800",{"key":27,"text":476,"correct":29},"1800",{"key":31,"text":478,"correct":22},"3200",{"id":480,"libraryId":5,"type":15,"typeLabel":16,"stem":481,"options":482,"answer":27,"analysis":33},932690,"某新建轻型木结构建筑，其最大允许建筑层数为（ ）层。",[483,484,485,486],{"key":20,"text":87,"correct":22},{"key":24,"text":91,"correct":22},{"key":27,"text":181,"correct":29},{"key":31,"text":183,"correct":22},{"id":488,"libraryId":5,"type":489,"typeLabel":490,"stem":491,"options":492,"answer":504,"analysis":33},932691,2,"多选题","某一级耐火等级的物流建筑，地上2层，层高为5m，主要功能为分拣电子用品为主，按照使用功能分为分拣作业区和储存区，采用防火墙完全分隔，该厂房全部设置有自动喷水灭火系统、火灾自动报警系统保护，则下列说法正确的有（ ）。",[493,495,497,499,501],{"key":20,"text":494,"correct":29},"该大楼的最多允许层数不限",{"key":24,"text":496,"correct":22},"分拣作业区的防火分区最大允许建筑面积不限",{"key":27,"text":498,"correct":29},"储存区的防火分区最大允许建筑面积为4800m2",{"key":31,"text":500,"correct":29},"储存区的最大允许占地面积为19200m2",{"key":502,"text":503,"correct":22},"E","分拣作业区的防火分区最大允许建筑面积为24000m2","ACD",{"id":506,"libraryId":5,"type":489,"typeLabel":490,"stem":507,"options":508,"answer":519,"analysis":33},932692,"某大型地下2层商场，每层建筑面积为23000m2，装修材料全部采用不燃材料，设置自动喷水灭火系统和火灾自动报警系统保护，则下列关于该商场的说法正确的有（ ）。",[509,511,513,515,517],{"key":20,"text":510,"correct":22},"应采用无门、窗、洞口的防火墙，耐火极限不低于1．50h的不燃性楼板分隔为多个商场",{"key":24,"text":512,"correct":29},"相邻区域局部连通时，可采用避难走道和防火隔间",{"key":27,"text":514,"correct":22},"该商场的每个防火分区最大允许面积不应大于10000m2",{"key":31,"text":516,"correct":29},"必要时可以采用下沉式广场连通",{"key":502,"text":518,"correct":22},"采用防烟楼梯间相连通时采用乙级防火门","BD",{"id":521,"libraryId":5,"type":489,"typeLabel":490,"stem":522,"options":523,"answer":534,"analysis":33},932693,"某商业建筑，建筑高度30m，地上6层，层高5m，建筑面积6000m2，中部设置一个面积为3000m2、贯穿建筑一至五层的中庭，下列关于该中庭的做法，正确的是（ ）。",[524,526,528,530,532],{"key":20,"text":525,"correct":29},"采用耐火极限为3．00h的防火卷帘与周围空间分隔",{"key":24,"text":527,"correct":22},"中庭内设有机械防烟设施",{"key":27,"text":529,"correct":29},"中庭环廊内设有自动喷水灭火系统和点型感烟火灾探测器",{"key":31,"text":531,"correct":22},"相连通的门、窗，应采用火灾时能自行关闭的乙级防火门、窗",{"key":502,"text":533,"correct":22},"中庭下设有大型儿童充气城堡","AC",{"id":536,"libraryId":5,"type":489,"typeLabel":490,"stem":537,"options":538,"answer":549,"analysis":33},932694,"建筑发生火灾时，烟气流动的方向通常是火势蔓延的一个主要方向。下列关于烟气扩散的说法，正确的有（ ）。",[539,541,543,545,547],{"key":20,"text":540,"correct":29},"烟气扩散流动速度与烟气温度和流动方向有关",{"key":24,"text":542,"correct":29},"烟气在水平方向的扩散流动速度较小",{"key":27,"text":544,"correct":22},"烟气在垂直方向的扩散流动速度较大，通常为6～8m／s",{"key":31,"text":546,"correct":29},"在管道竖井中，烟气上升流动速度很大",{"key":502,"text":548,"correct":22},"当高层建筑发生火灾时，烟气在其内的流动扩散路线中最主要的一条是着火房间→相邻上层房间→室外","ABD",{"id":551,"libraryId":5,"type":489,"typeLabel":490,"stem":552,"options":553,"answer":564,"analysis":33},932695,"厂房的防火分区建筑面积的确定因素有（ ）。",[554,556,558,560,562],{"key":20,"text":555,"correct":29},"厂房的层数",{"key":24,"text":557,"correct":22},"连续生产线工艺布置情况",{"key":27,"text":559,"correct":29},"厂房的耐火等级",{"key":31,"text":561,"correct":22},"厂房内灭火救援设施的布置情况",{"key":502,"text":563,"correct":29},"生产的火灾危险性类别","ACE",{"id":566,"libraryId":5,"type":489,"typeLabel":490,"stem":567,"options":568,"answer":579,"analysis":33},932696,"建筑的防火墙防止火灾蔓延至相邻区域且耐火极限不低于3．00h的不燃性墙体，防火墙不宜设置在转角处，确需设置时，下列设置符合规范要求的有（ ）。",[569,571,573,575,577],{"key":20,"text":570,"correct":22},"内转角两侧墙上的门、窗、洞口之间最近边缘的水平距离为3．0m",{"key":24,"text":572,"correct":29},"内转角两侧墙上的门、窗、洞口之间最近边缘的水平距离为4．0m",{"key":27,"text":574,"correct":29},"内转角两侧墙上的门、窗、洞口之间最近边缘的水平距离为5．0m",{"key":31,"text":576,"correct":29},"内转角两侧墙上为乙级防火窗时，距离为4m",{"key":502,"text":578,"correct":29},"内转角两侧墙上为乙级防火窗时，距离为2m","BCDE",{"id":581,"libraryId":5,"type":489,"typeLabel":490,"stem":582,"options":583,"answer":594,"analysis":33},932697,"下列关于不同耐火等级民用建筑不设置自喷情况下防火分区的最大允许建筑面积，说法正确的是（ ）。",[584,586,588,590,592],{"key":20,"text":585,"correct":29},"一、二级耐火等级的高层民用建筑防火分区的最大允许建筑面积为1500m2",{"key":24,"text":587,"correct":22},"一、二级耐火等级的单、多层民用建筑防火分区的最大允许建筑面积为3000m2",{"key":27,"text":589,"correct":22},"一级耐火等级的地下或半地下建筑（室）防火分区的最大允许建筑面积为400m2",{"key":31,"text":591,"correct":29},"三级耐火等级的单、多层民用建筑防火分区的最大允许建筑面积为1200m2",{"key":502,"text":593,"correct":29},"四级耐火等级的单、多层民用建筑防火分区的最大允许建筑面积为600m2","ADE",{"id":596,"libraryId":5,"type":15,"typeLabel":16,"stem":597,"options":598,"answer":24,"analysis":33},932698,"下列防火分隔措施中，不属于横向防火分区分隔物的是（ ）。",[599,601,603,605],{"key":20,"text":600,"correct":22},"防火隔墙",{"key":24,"text":602,"correct":29},"防火挑檐",{"key":27,"text":604,"correct":22},"防火门",{"key":31,"text":606,"correct":22},"防火水幕",{"id":608,"libraryId":5,"type":15,"typeLabel":16,"stem":609,"options":610,"answer":27,"analysis":33},932699,"下列关于工业建筑耐火等级的说法中，正确的是（ ）。",[611,613,615,617],{"key":20,"text":612,"correct":22},"建筑高度大于24m的非单层厂房的耐火等级不应低于一级",{"key":24,"text":614,"correct":22},"对于火灾危险性较大的甲、乙类厂房，其耐火等级不应低于一级",{"key":27,"text":616,"correct":29},"丙类厂房当为单层时，其耐火等级不应低于三级",{"key":31,"text":618,"correct":22},"丁、戊类厂房（仓库）当为多层时，其耐火等级不应低于二级",[620,623,626,629,632,635],{"id":15,"name":621,"category":7,"favorite":622},"领导干部任职前廉政法规知识测试题",92,{"id":624,"name":625,"category":7,"favorite":15},595,"建筑结构与设备",{"id":627,"name":628,"category":7,"favorite":15},715,"招标采购专业知识与法律法规",{"id":630,"name":631,"category":7,"favorite":15},848,"市政方向-通用基础",{"id":633,"name":634,"category":7,"favorite":8},534,"BIM工程师",{"id":636,"name":634,"category":7,"favorite":8},535]