[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934542":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},934542,604,1,"单选题","防火分隔部位设置防火卷帘时，不符合规范规定的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","除中庭外，当防火分隔部位的宽度不大于30m时，防火卷帘的宽度不应大于10m，当防火分隔部位的宽度大于30m时，防火卷帘的宽度不应大于该部位宽度的1\u002F2，且不应大于20m",true,{"key":16,"text":17,"correct":18},"B","防火卷帘应具有火灾时靠自重自动关闭功能。",false,{"key":20,"text":21,"correct":18},"C","当防火卷帘的耐火极限符合现行国家标准《门和卷帘的耐火试验方法》GB\u002FT7633有关耐火完整性和耐火隔热性的判定条件时，可不设置自动喷水灭火系统保护。",{"key":23,"text":24,"correct":18},"D","当防火卷帘的耐火极限仅符合现行国家标准《门和卷帘的耐火试验方法》GB\u002FT7633有关耐火完整性的判定条件时，应设置自动喷水灭火系统保护。","参考《建规》6.5.3：“除中庭外，当防火分隔部位的宽度不大于30m时，防火卷帘的宽度不应大于10m：当防火分隔部位的宽度大于30m时，防火卷帘的宽度不应大于该防火分隔部位宽度的1\u002F3，且不应大于20m。”防火分隔＞30m，卷帘长度=MⅠn（1\u002F3，20）：故A的1\u002F2错误。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]