[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934509":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},934509,604,1,"单选题","如受条件限制，必须将油浸电力变压器室布置在民用建筑主体建筑内时，下列防火措施（ ）是错误的。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","不应布置在人员密集场所的上一层、下一层或贴临",false,{"key":16,"text":17,"correct":14},"B","疏散门应直通室外或安全出口",{"key":19,"text":20,"correct":14},"C","与其他部位之间应采用耐火极限不低于2.00h的防火隔墙和1.50h的不燃性楼板分隔",{"key":22,"text":23,"correct":24},"D","储油间应采用耐火极限不低于2.00h的防火隔墙与锅炉间分隔",true,"参考《建规》5-4.12：“确需布置在民用建筑内时，不应布置在人员密集场所的上一层、下一层或贴邻，并应符合下列规定：2锅炉房、变压器室的疏散门均应直通室外或安全出口。3锅炉房、变压器室等与其他部位之间应采用耐火极限不低于2.00h的防火隔墙和1.50h的不燃性楼板分隔；4储油间应采用耐火极限不低于3.00h的防火隔墙与锅炉间分隔。”故D错误，应为3.0h。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]