[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934486":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},934486,604,1,"单选题","关于建筑防火设计的说法中，错误的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","卡拉0K厅各厅室之间采用耐火极限为2.00h的防火隔墙和1.5h的不燃烧性楼板及乙级防火门分隔",false,{"key":16,"text":17,"correct":18},"B","柴油发电机房内的储油间（柴油储量为0.8m3），采用耐火极限为2.50h的防火隔墙和1.50h的不燃烧性楼板及甲级防火门与其他部位分隔",true,{"key":20,"text":21,"correct":14},"C","高层住宅建筑下部设置的商业服务网点，采用耐火极限为2.50h且无门、窗、洞口的防火隔墙和1.50h的不燃烧性楼板与其他部位分隔",{"key":23,"text":24,"correct":14},"D","医院病房楼内相邻护理单元之间采用耐火极限为2.00h的防火隔墙和乙级防火门分隔","参考《建规》5.4.12-4:“锅炉房内设置储油间时，其总储存量不应大于1m3，且储油间应采用耐火极限不低于3.00h的防火隔墙与锅炉间分隔。”2.5h防火隔墙错误，故B错误。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]