[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934485":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},934485,604,1,"单选题","燃气、燃油锅炉房设置在高层建筑物内，下述不符合规定的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","不应布置在人员密集场所的上一层、下一层，但采用耐火极限不低于2.00h的隔墙可贴邻布置",true,{"key":16,"text":17,"correct":18},"B","采用无门窗洞口的耐火极限不低于2.00h的隔墙和1.50h的楼板与其他部位隔开。当必须开门时，应设甲级防火门",false,{"key":20,"text":21,"correct":18},"C","应布置在首层或地下一层靠外墙部位",{"key":23,"text":24,"correct":18},"D","锅炉房内设置储油间时，其总储存量不应大于1m3","参考《建规》5.4.12：“宜设置在建筑外的专用房间内；确需贴邻民用建筑布置时，应采用防火墙与所贴邻的建筑分隔，确需布置在民用建筑内时，不应布置在人员密集场所的上一层、下一层或贴邻，并应符合下列规定：1燃油或燃气锅炉房、变压器室应设置在首层或地下一层的靠外墙部位。3锅炉房、变压器室等与其他部位之间应采用耐火极限不低于2.00h的防火隔墙和1.50h的不燃性楼板分隔。在隔墙和楼板上不应开设洞口，确需在隔墙上设置门、窗时，应采用甲级防火门、窗。4锅炉房内设置储油间时，其总储存量不应大于1m3，且储油间应采用耐火极限不低于3.00h的防火隔墙与锅炉间分隔。”选项A，应该是“，应采用防火墙与所贴邻的建筑分隔”，故A错误。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]