[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934481":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},934481,604,1,"单选题","一、二级耐火等级建筑内的商店营业厅、展览厅设置在单层建筑或仅设置在多层建筑的首层内时，设置自动灭火系统和火灾自动报警系统并采用不燃或难燃装修材料，其每个防火分区的最大允许建筑面积为（ ）m2。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","5000m2",false,{"key":16,"text":17,"correct":14},"B","4000m2",{"key":19,"text":20,"correct":21},"C","10000m2",true,{"key":23,"text":24,"correct":14},"D","2000m2","参考《建规》5.3.4：“一、二级耐火等级建筑内的商店营业厅、展览厅，当设置自动灭火系统和火灾自动报警系统并采用不燃或难燃装修材料时，其每个防火分区的最大允许建筑面积应符合下列规定：1 设置在高层建筑内时，不应大于4000m2。2 设置在单层建筑或仅设置在多层建筑的首层内时，不应大于10000m2。”故C正确。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]