[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934364":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},934364,604,2,"多选题","某丙类厂房建筑高度为45m，对其消防救援窗口进行防火检查。下列消防救援窗口设置的做法中，符合规范要求的有（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","消防救援窗口采用易碎安全玻璃，并在外侧设置明显标志",true,{"key":16,"text":17,"correct":18},"B","每个防火分区设置1个消防救援窗口",false,{"key":20,"text":21,"correct":18},"C","消防救援窗口设置在3层以上楼层",{"key":23,"text":24,"correct":14},"D","消防救援窗口的净高和净宽均为1.20m",{"key":26,"text":27,"correct":14},"E","消防救援窗口的下沿距地面室内高度为1.2m","ADE","选项A、B、D、E，参考《建规》7.2.5：“供消防救援人员进入的窗口的净高度和净宽度均不应小于1.0m，下沿距室内地面不宜大于1.2m，间距不宜大于20m且每个防火分区不应少于2个，设置位置应与消防车登高操作场地相对应。窗口的玻璃应易于破碎，并应设置可在室外易于识别的明显标志”，故A、D、E正确，B错误：选项C，参考《建规》7.2.4：“厂房、仓库、公共建筑的外墙应在每层的适当位置设置可供消防救援人员进入的窗口”，故C错误。",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]