[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934353":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},934353,604,2,"多选题","下列关于消防电梯的叙述中，错误的是（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","消防电梯应分别设置在不同防火分区内，且每个防火分区不应少于1台",false,{"key":16,"text":17,"correct":18},"B","消防电梯可以作为一个安全出口",true,{"key":20,"text":21,"correct":18},"C","建筑高度大于32m的高层厂房（仓库），每个防火分区内宜设置1台消防电梯",{"key":23,"text":24,"correct":14},"D","消防电梯前室的使用面积不应小于6m2",{"key":26,"text":27,"correct":18},"E","与防烟楼梯间合用的前室，不应小于10m2","BCE","参考《建规》7.3.2，消防电梯应分别设置在不同防火分区内，且每个防火分区不应少于1台，A正确：参考《建规》5.5.4，自动扶梯和电梯不应计作安全疏散设施，B错误：参考《建规》7.3.3，建筑高度大于32m且设置电梯的高层厂房（仓库），每个防火分区内宜设置1台消防电梯，C错误：参考《建规》7.3.5，消防电梯前室的使用面积不应小于6.0m2，D正确；参考《建规》7.3.5，前室的使用面积不应小于6m2；与防烟楼梯间合用的前室，公共建筑不应小于10m2，居住建筑不应小于6m2，E选项未明确公共建筑还是住宅建筑，故E错误：",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]