[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934047":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},934047,604,1,"单选题","下列有关人防工程中水泵接合器和室外消火栓的说法中，不正确的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","当人防工程内消防用水总量大于10L／s时，应在人防工程外设置水泵接合器",false,{"key":16,"text":17,"correct":14},"B","每个水泵接合器和室外消火栓的流量应按10～15L／s计算",{"key":19,"text":20,"correct":14},"C","水泵接合器与室外消火栓的距离不应大于40m",{"key":22,"text":23,"correct":24},"D","水泵接合器距人防工程出入口不宜小于15m",true,"根据《人民防空工程设计防火规范》GB 50098—20097．5．1，当人防工程内消防用水总量大于10L／s时，应在人防工程外设置水泵接合器，并应设置室外消火栓，A选项正确；根据7．5．2，水泵接合器和室外消火栓的数量，应按人防工程内消防用水总量确定，每个水泵接合器和室外消火栓的流量应按（10～15）L／s计算，B选项正确；根据7．5．3，水泵接合器和室外消火栓应设置在便于消防车使用的地点，距人防工程出入口不宜小于5m；室外消火栓距路边不宜大于2m，水泵接合器与室外消火栓的距离不应大于40m，C选项正确，D选项错误。本题答案为D。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]