[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934042":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},934042,604,2,"多选题","某商业建筑，建筑高度为23．3m，地上标准层每层划分为面积相近的2个防火分区，防火分隔部位的宽度为60m，该商业建筑的下列防火分隔做法中，正确的有（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","防火墙设置两个不可开启的乙级防火窗",false,{"key":16,"text":17,"correct":14},"B","防火墙上设置两樘常闭式乙级防火门",{"key":19,"text":20,"correct":21},"C","设置总宽度为18m、耐火极限为3．00h的特级防火卷帘",true,{"key":23,"text":24,"correct":21},"D","采用耐火极限为3．00h的不燃性墙体从楼地面基层隔断至梁或楼板地面基层",{"key":26,"text":27,"correct":14},"E","通风管道在穿越防火墙处设置一个排烟防火阀","CD","根据《建筑设计防火规范》GB 50016-2014（2018年版）中6．1．1，防火墙应直接设置在建筑的基础或框架、梁等承重结构上，框架、梁等承重结构的耐火极限不应低于防火墙的耐火极限。D正确。 根据6．1．5，防火墙上不应开设门、窗、洞口，确需开设时，应设置不可开启或火灾时能自动关闭的甲级防火门、窗。可燃气体和甲、乙、丙类液体的管道严禁穿过防火墙。防火墙内不应设置排气道。ABE错误。 根据6．5．3 -1.1除中庭外，当防火分隔部位的宽度不大于30m时，防火卷帘的宽度不应大于10m；当防火分隔部位的宽度大于30m时，防火卷帘的宽度不应大于该部位宽度的1／3，且不应大于20m。C正确。因此，本题的正确答案为CD。",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]