[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934032":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},934032,604,1,"单选题","下列关于数据中心灭火系统选择的说法中，错误的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","A级数据中心的主机房宜设置气体灭火系统",false,{"key":16,"text":17,"correct":14},"B","A级数据中心的主机房可设置细水雾灭火系统",{"key":19,"text":20,"correct":14},"C","B级数据中心的主机房可设置自动喷水灭火系统",{"key":22,"text":23,"correct":24},"D","总控中心等长期有人工作的区域应设置细水雾灭火系统",true,"根据《数据中心设计规范》GB50174—201713．1．2，A级数据中心的主机房，宜设置气体灭火系统，也可设置细水雾灭火系统，AB选项正确；根据13．1．3，B级数据中心和C级数据中心的主机房宜设置气体灭火系统，也可设置细水雾灭火系统或自动喷水灭火系统，C选项正确；根据13．1．4，总控中心等长期有人工作的区域应设置自动喷水灭火系统，D选项错误。本题答案为D。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]