[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934013":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},934013,604,1,"单选题","下列关于洁净厂房内静电防护措施及接地措施的说法中错误的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","洁净室的净化空调系统应采取防静电接地措施",false,{"key":16,"text":17,"correct":14},"B","在防静电接地系统各个连接部位之间电阻值应小于0．1Ω",{"key":19,"text":20,"correct":14},"C","接地系统采用综合接地方式时接地电阻值应小于或等于1Ω",{"key":22,"text":23,"correct":24},"D","选择分散接地方式时，各种功能接地系统的接地体必须远离防雷接地系统的接地体，两者应保持30m以上的间距",true,"根据《洁净厂房设计规范》GB 50073—20139．5．7，接地系统采用综合接地方式时接地电阻值应小于或等于1Ω：选择分散接地方式时，各种功能接地系统的接地体必须远离防雷接地系统的接地体，两者应保持20m以上的间距。洁净厂房的防雷接地系统设计应符合现行国家标准《建筑物防雷设计规范》GB 50057的有关规定，C选项正确，D选项错误；根据9．5．3，洁净室的净化空调系统应采取防静电接地措施，A选项正确；根据9．5．5，在防静电接地系统各个连接部位之间电阻值应小于0．1Ω，C选项正确。本题答案为D。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]