[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934001":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},934001,604,1,"单选题","下列关于洁净厂房的防火和疏散说法错误的是（ ）",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","洁净厂房的耐火等级不应低于二级",false,{"key":16,"text":17,"correct":14},"B","顶棚的耐火极限不应低于0．4h，疏散走道顶棚的耐火极限不应低于1．0h",{"key":19,"text":20,"correct":14},"C","隔墙及其相应顶棚的耐火极限不应低于1h，隔墙上的门窗耐火极限不应低于0．6h",{"key":22,"text":23,"correct":24},"D","穿过隔墙或顶棚的管线周围空隙应采用非燃烧材料紧密填塞，技术竖井井壁应为非燃烧体，其耐火极限不应低于2h",true,"根据《洁净厂房设计规范》（GB50073—2013）第5．2．1条规定，洁净厂房的耐火等级不应低于二级。根据第5．2．4条规定，洁净室的顶棚、壁板及夹芯材料应为不燃烧体，且不得采用有机复合材料。顶棚和壁板的耐火极限不应低于0．4h，疏散走道顶棚的耐火极限不应低于1．0h。根据第5．2．5条规定，在一个防火分区内的综合性厂房，洁净生产区与一般生产区域之间应设置不燃烧体隔断措施。隔墙及其相应顶棚的耐火极限不应低于1h，隔墙上的门窗耐火极限不应低于0．6h。穿隔墙或顶板的管线周围空隙应采用防火或耐火材料紧密填堵。根据第5．2．6条规定，技术竖井井壁应为不燃烧体，其耐火极限不应低于1h。井壁上检查门的耐火极限不应低于0．6h；竖井内在各层或间隔一层楼板处，应采用相当于楼板耐火极限的不燃烧体作水平防火分隔；穿过水平防火分隔的管线周围空隙应采用防火或耐火材料紧密填堵。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]